NeoTherm Boilers and Water Heaters
Page 17
Section 5
PUmP reQUIrementS
5.1
neotherm Boiler flow and Head requirements
5.2
neotherm Water Heater flow and Head requirements
table 7 - Water flow requirements
table 8 - neotherm Water Heater flow Data
Temperature Rise in °F
20°F
25°F
30°F
35°F
40°F
45°F
Flow
GPM
H/L-Ft
Flow
GPM
H/L-Ft
Flow
GPM
H/L-Ft
Flow
GPM
H/L-
Ft
Flow
GPM
H/L-Ft
Flow
GPM
H/L-Ft
95
30
75
20
62
15
54
11
48
9
42
7
Temperature Rise in °c
11.0°c
13.7°c
16.5°c
19.3°c
22.0°c
24.7°c
Flow
LPm
H/L-m
Flow
LPm
H/L-m
Flow
LPm
H/L-m
Flow
LPm
H/L-m
Flow
LPm
H/L-m
Flow
LPm
H/L-m
359
9.0
283
6.0
234
4.5
204
3.3
182
2.7
159
2.1
Temperature Rise
20°F
11.0°c
Flow GPM
H/L-Ft
Flow LPm
H/L-m
95
30
359
9.0
Notes -
Figures listed are for soft/normal water.
Maximum hardness of 10 grains per gallon allowed.
Summary of Contents for NTV1000
Page 2: ......
Page 35: ...NeoTherm Boilers and Water Heaters Page 31 Fig 20 Ladder Diagram...
Page 36: ...LAARS Heating Systems Page 32 Fig 21 Wiring Diagram...
Page 37: ...NeoTherm Boilers and Water Heaters Page 33...
Page 51: ...NeoTherm Boilers and Water Heaters Page 47 Fig 52 Connection Terminals...
Page 130: ...LAARS Heating Systems Page 126 Fig 140 Machine Frame and Rear Panel 13 3 PARTS ILLUSTRATIONS...
Page 131: ...NeoTherm Boilers and Water Heaters Page 127 Fig 141 Front Panel and Covers...
Page 132: ...LAARS Heating Systems Page 128 Fig 142 Burners and Combustion Chambers...
Page 134: ...LAARS Heating Systems Page 130 Fig 145 Electronic Components...
Page 135: ...NeoTherm Boilers and Water Heaters Page 131 Fig 146 Condensate Trap Fig 147 Control Bezel...
Page 136: ...LAARS Heating Systems Page 132 Fig 148 Flow Switch...
Page 137: ...NeoTherm Boilers and Water Heaters Page 133 This page intentionally left blank...