Page 70
LAARS Heating Systems
192
Invalid igniter
on during setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
193
Invalid ignite
failure delay
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
194
Invalid ignite
failure response
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.\
195
Invalid ignite
failure retries
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
196
Invalid ignition
source setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
197
Invalid interlock
open response
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
198
Invalid interlock
start check
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
199
Invalid LCI
(Limit Control
Input) enable
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
200
Invalid lightoff
rate setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
201
Invalid lightoff
rate proving
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
202
Invalid MFEP
(Main Flame
Establishing
Period) time
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
Summary of Contents for NTV
Page 4: ...LAARS Heating Systems...
Page 11: ...Page 7 NEOTHERM Boilers and Water Heaters...
Page 24: ...Page 20 LAARS Heating Systems Figure 16 Hydronic Piping Single Boiler Zoning with Circulators...
Page 84: ...Page 80 LAARS Heating Systems Parts Illustration 1 Jacket Components...
Page 86: ...Page 82 LAARS Heating Systems Parts Illustration 4 Internal Components Sizes 750 850...
Page 88: ...Page 84 LAARS Heating Systems Parts Illustration 6 Gas Train Components Sizes 600 850...
Page 91: ...Page 87 NEOTHERM Boilers and Water Heaters Notes...