Boilers and Water Heaters
109
Ignition failed
L
1. Check main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, fl ame detector, fl ame detector
siting or fl ame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the module.
110
Ignition failure
occurred
H
Hold time of recycle and hold option. Will not be a lockout fault. Hold
Only. Internal hardware test. Not a lockout.
111
Flame current
lower than weak
threshold
H
Hold time of recycle and hold option. Will not be a lockout fault. Hold
Only. Internal hardware test. Not a lockout.
113
Flame circuit
timeout
L
Flame sensed during Initiate or off cycle, hold 240 seconds, if present
after 240 seconds, system will lockout.
119
Control
Interaction Fault
H
Flap valve identifi cations confi gured incorrectly.
122
Lightoff rate
proving failed
L
1. Check wiring and correct any potential wiring errors.
2. Check VFD’s (Variable-speed Fan Drive) ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
123
Purge rate
proving failed
L
1. Check wiring and correct any potential wiring errors.
2. Check VFD’s (Variable-speed Fan Drive) ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
128
Fan speed failed
during prepurge
H or L 1. Check wiring and correct any potential wiring errors.
2. Check the VFDs (Variable-speed Fan Drive) ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
129
Fan speed
failed during
preignition
H or L 1. Check wiring and correct any potential wiring errors.
2. Check the VFDs (Variable-speed Fan Drive) ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
130
Fan speed failed
during ignition
H or L 1. Check wiring and correct any potential wiring errors.
2. Check the VFDs (Variable-speed Fan Drive) ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
131
Fan movement
detected during
standby
H
1. Check wiring and correct any potential wiring errors.
2. Check the VFDs (Variable-speed Fan Drive) ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
132
Fan speed failed
during run
H
1. Check wiring and correct any potential wiring errors.
2. Check the VFDs (Variable-speed Fan Drive) ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
137
ILK (Interlock)
failed to close
H
1. Check wiring and correct any possible shorts.
2. Check Interlock (ILK) switches to assure proper function.
3. Verify voltage through the interlock string to the interlock input with a
voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the module.
Summary of Contents for NTV
Page 4: ...LAARS Heating Systems...
Page 11: ...Page 7 NEOTHERM Boilers and Water Heaters...
Page 24: ...Page 20 LAARS Heating Systems Figure 16 Hydronic Piping Single Boiler Zoning with Circulators...
Page 84: ...Page 80 LAARS Heating Systems Parts Illustration 1 Jacket Components...
Page 86: ...Page 82 LAARS Heating Systems Parts Illustration 4 Internal Components Sizes 750 850...
Page 88: ...Page 84 LAARS Heating Systems Parts Illustration 6 Gas Train Components Sizes 600 850...
Page 91: ...Page 87 NEOTHERM Boilers and Water Heaters Notes...