Section 3 -
VENTING AND COMBUSTION AIR
3.1 General Venting
This product requires a special venting system. Refer to
venting supplier’s instructions for complete parts list and
method of installation. The manufacturers and product lines
listed on the following tables have been tested and authorized
to safely operate with Laars equipment. Suppliers of stainless
steel and polypropylene venting that are not listed on these
tables are not permitted for use with Laars vent
category III/ IV products.
NOTES:
1.
“x”, “xx”, and “xxxx” refer to variations in nominal size. See manufacturer’s catalog for a particular application.
Table 4. Allowable Single Wall Stainless Steel Vent Suppliers and Part Numbers
Table 5. Allowable Polypropylene Vent Manufacturers / Trade Names
Do not mix venting suppliers and models in venting systems.
Failure to comply could result in personal injury, property
damage, or death.
Installations must comply with applicable national, state and
local codes.
ALLOWABLE SINGLE WALL STAINLESS STEEL VENT SUPPLIERS AND PART NUMBERS
Selkirk
DuraVent
NovaFlex
Safe-T Vent EZ Seal
FasNSeal
Z Flex
90° Elbow
9x14
FSELB90xx
2SVEExx90
Pipe
9x07
FSVLxxxx
2SVEPxxxx
Boiler Adapter
5x01BOI
FSAAUx
2SVSAxx (OD)
2SVSTTAxx (ID)
Horizontal Termination (bird screen
9x92
FSBSx
2SVSTPXxx
Vertical Termination (rain cap)
5X00CI
FSRCx
2SVSRCxx
Inlet Air Termination
9xTERM
FSAIHXX*
2SVSTEXxx90
Adapter, SS to CPVC
FSA-xxFNSM-xPVCF
Adapter SS to PP
FSAAUx-xPP
2ZDCPVCx**
*4", 6" & 7" only
**up to 6"
ALLOWABLE POLYPROPYLENE VENT MANUFACTURERS / TRADE NAMES
CentroTherm
DuraVent
Selkirk
NovaFlex
InnoFlue
PolyPro
PolyFlue
Z-Dens
Single Wall Pipe
ISVLxxxx
xPPS-x
83x002
ZDPx
Elbow
ISELxxxx
xPPS-E90L
83x08
2ZDEx87
PVC Adapter
ISAGLxxxx
xPPS-ADL (to 4")
xPPS-xxPVCM-xPPF (>4")
83x040
2ZDCPVCx
Horizontal Termination
(bird screen)
IASPPxx (2" - 4")
IASSSxx (5" - 12")
xPPS-BG (2" - 6")
83x050
2ZDESx
Vertical Termination
IASPPxx (2" - 4")
IASSSxx (5" - 12")
xPPS-VKL (<5")
xPPS-VTML (5"-8")
83x050
2ZDESx
Air Inlet
2ZDESx
MFR MODEL NUMBER (ABBREVIATED)
MFR MODEL NUMBER (ABBREVIATED)
Trade Name / Model
Example Components
Example Components
Trade Name / Model
3.2 Combustion Air
NeoTherm boilers and water heaters must have provisions
for combustion and ventilation air in accordance with the
applicable requirements for Combustion Air Supply and
Ventilation in the National Fuel Gas Code, ANSI Z223 1; or in
Canada, the Natural Gas and Propane Installation Code, CSA
B149.1. All applicable provisions of local building codes must
also be adhered to.
A NeoTherm unit can take combustion air from the space
in which it is installed, or the combustion air can be ducted
directly to the unit. Ventilation air must be provided in either
case.
Summary of Contents for NTV
Page 4: ...LAARS Heating Systems...
Page 11: ...Page 7 NEOTHERM Boilers and Water Heaters...
Page 24: ...Page 20 LAARS Heating Systems Figure 16 Hydronic Piping Single Boiler Zoning with Circulators...
Page 84: ...Page 80 LAARS Heating Systems Parts Illustration 1 Jacket Components...
Page 86: ...Page 82 LAARS Heating Systems Parts Illustration 4 Internal Components Sizes 750 850...
Page 88: ...Page 84 LAARS Heating Systems Parts Illustration 6 Gas Train Components Sizes 600 850...
Page 91: ...Page 87 NEOTHERM Boilers and Water Heaters Notes...