Page 57
N
EO
T
HERM
Boilers and Water Heaters
factory for proper trouble shooting practices prior to replacing
the control. If control replacement is required, turn off all
power to the appliance and shut off all manual gas valves
to the appliance. Remove the front door to the appliance
and the plastic bezel and the control panel. Remove all
wire connections from the control board. The control board
connections are keyed to only allow connection in the proper
location, but proper handling techniques should be used to
avoid damage to the wiring or connectors. To remove the
control, push in on the two tabs on the left side of the board
to unlatch the clips from the control panel. Rotate the control
around the fastening points on the right side of the control
to remove the hooks from the control panel. To replace the
control, repeat the steps listed above in the reverse orders
making sure to connect all wires in the proper locations. Place
the appliance in operation following the steps outlined in
Section 9.
Ignitor Assembly
The ignitor assembly is a two rod system that consists of a
ground rod and a spark rod (See Figure 47). To remove the
ignitor assembly, shut off the 120 Volt power supply to the
appliance. Turn off all manual gas valves connecting the
appliance to the main gas supply line. Remove the front door
of the boiler to gain access to the ignitor assembly. Remove
the two wires connected to the assembly. Then remove the
two bolts connecting the ignitor assembly to the burner door.
If the old ignitor assembly is determined to be defective,
install a new ignitor assembly (check that the spark gap is
3/16”). Replace the gasket if necessary.
Flame Sensor
The flame sensor is a single rod system. To replace the flame
sensor electrode, shut off the 120 Volt power supply to the
boiler. Turn off all manual gas valves connecting the boiler
to the main gas supply line. Remove the front door of the
boiler to gain access to the flame sensor electrode. Remove
the flame sensor wire from the electrode. Remove the two
bolts fastening the electrode to the burner doors. Remove
and replace the old flame sensor gasket. If the old electrode
is determined to be defective, install a new flame sensor
electrode in the reverse order.
Figure 47 - Burner Service
NOTES:
SPARK IGNITOR
1.
GIANNONI #gm10-35-108-01
1.08
.18
W20131
3.1
3/16”
Ignitor Assembly
Summary of Contents for NTV
Page 4: ...LAARS Heating Systems...
Page 11: ...Page 7 NEOTHERM Boilers and Water Heaters...
Page 24: ...Page 20 LAARS Heating Systems Figure 16 Hydronic Piping Single Boiler Zoning with Circulators...
Page 84: ...Page 80 LAARS Heating Systems Parts Illustration 1 Jacket Components...
Page 86: ...Page 82 LAARS Heating Systems Parts Illustration 4 Internal Components Sizes 750 850...
Page 88: ...Page 84 LAARS Heating Systems Parts Illustration 6 Gas Train Components Sizes 600 850...
Page 91: ...Page 87 NEOTHERM Boilers and Water Heaters Notes...