NeoTherm LC Boilers and Water Heaters
Page 69
2. Set the outdoor reset and warm weather
shutdown parameters as desired.
How to get there – Outdoor Reset Screen and Warm
Weather Shutdown Screen
Home Page <Press View Lead/ Lag button> Lead/ Lag
Screen <Press Lead/ Lag Master button> Lead/ Lag
Screen <Press Configure button> Lead/ Lag Master
Configuration Screen <Press Advanced Settings button>
Select the Outdoor Reset Screen or the Warm Weather
Shutdown Screen
Fig. 92 – Outdoor Reset
For a detailed explanation of the Outdoor
Reset function, see the section titled “About
Outdoor Reset” which follows.
Fig. 93 – Warm Weather Shutdown
When enabled, the Warm Weather Shutdown
feature will turn off the Central Heating
functions when the outdoor temperature
exceeds the setpoint. This prevents the system
from running when there is no need for heat.
Enable -
These options determine how quickly
the system shuts down after the outdoor
temperature rises above the setpoint. The
options are Shutdown immediately/ After
demand ends/ Disabled.
Setpoint -
If the outdoor temperature is higher than
this, the system will shut off the Lead/Lag
Central Heating functions.
About Outdoor Reset
The Outdoor Reset feature calculates a correction
for the Lead/Lag setpoint depending on the outdoor
temperature. This allows the system to adjust for
changes in the outdoor temperature and run more
efficiently.
The Show Line button at the bottom of the Outdoor
Reset screen displays a curve which shows
how the system will behave at different outdoor
temperatures. See Fig. 94.
Fig. 94 – Show Line Screen
The display shown above show the action of the
system with one possible group of settings. The
green line shows the setpoint used by the system.
• Without Outdoor Reset, this would be a
constant 120°F (or whatever value you chose),
regardless of the outdoor temperature. The
green line in the graph would run straight
across the display.
•
However, with the Outdoor Reset feature
turned on, the system will adjust for changes
in the outdoor temperature. Let’s take a
detailed look at behavior of the setpoint,
shown by the green line in the display. For
cold outdoor temperatures (below 32°F), the
setpoint remains unchanged (120°F). As the
temperature begins to rise above 32°F, the
Outdoor Reset function causes the setpoint to
be lowered. At these warmer temperatures,
the heating load on the system is not as great,
so the system does not have to reach as high
a temperature to handle the load. As you can
see from the display, at an outdoor temperature
of about 70°F, the system stops adjusting the
setpoint. Above 70°F, the setpoint is constant
at 100°F.
Summary of Contents for NTH1000
Page 4: ...LAARS Heating Systems ...
Page 11: ...NeoTherm LC Boilers and Water Heaters Page 7 Fig 6 Dimensions NT 1700 ...
Page 37: ...NeoTherm LC Boilers and Water Heaters Page 33 Fig 21 Ladder Diagram ...
Page 38: ...LAARS Heating Systems Page 34 Fig 22 Wiring Diagram ...
Page 39: ...NeoTherm LC Boilers and Water Heaters Page 35 ...
Page 51: ...NeoTherm LC Boilers and Water Heaters Page 47 Fig 51 Connection Terminals ...
Page 128: ...LAARS Heating Systems Page 124 Fig 140 Machine Frame NT1000 13 3 Parts Illustrations ...
Page 130: ...LAARS Heating Systems Page 126 Fig 143 Machine Frame NT1700 ...
Page 132: ...LAARS Heating Systems Page 128 Fig 145 Burners and Combustion Chamber NT1000 ...
Page 133: ...NeoTherm LC Boilers and Water Heaters Page 129 Fig 146 Burners and Combustion Chamber NT1700 ...
Page 135: ...NeoTherm LC Boilers and Water Heaters Page 131 Fig 149 Burner Detail NT1700 ...
Page 136: ...LAARS Heating Systems Page 132 Fig 150 Electronic Components Fig 151 Condensate Trap NT1000 ...
Page 138: ...LAARS Heating Systems Page 134 This page intentionally left blank ...
Page 139: ...NeoTherm LC Boilers and Water Heaters Page 135 This page intentionally left blank ...