LAARS Heating Systems
Page 100
Code Description
L or
H
Procedure
26
Internal fault:
Static flame ripple
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
27
Internal fault:
Flame rod shorted to ground detected
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
28
Internal fault:
A/D linearity test fails
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
29
Internal fault:
Flame bias cannot be set in range
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
30
Internal fault:
Flame bias shorted to adjacent pin
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
31
Internal fault:
SLO electronics unknown error
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
32-46 Internal fault:
Safety Key 0 through 14
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
47
Flame Rod to ground leakage
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
48
Static flame (not flickering)
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
49
24 VAC voltage low/high
H
1. Check the module and display connections.
2. Check the module power supply and make
sure that frequency, voltage and VA meet the
specifications.
50
Modulation fault
H
Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
51
Pump fault
H
Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
52
Motor tachometer fault
H
Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
Summary of Contents for NTH1000
Page 4: ...LAARS Heating Systems ...
Page 11: ...NeoTherm LC Boilers and Water Heaters Page 7 Fig 6 Dimensions NT 1700 ...
Page 37: ...NeoTherm LC Boilers and Water Heaters Page 33 Fig 21 Ladder Diagram ...
Page 38: ...LAARS Heating Systems Page 34 Fig 22 Wiring Diagram ...
Page 39: ...NeoTherm LC Boilers and Water Heaters Page 35 ...
Page 51: ...NeoTherm LC Boilers and Water Heaters Page 47 Fig 51 Connection Terminals ...
Page 128: ...LAARS Heating Systems Page 124 Fig 140 Machine Frame NT1000 13 3 Parts Illustrations ...
Page 130: ...LAARS Heating Systems Page 126 Fig 143 Machine Frame NT1700 ...
Page 132: ...LAARS Heating Systems Page 128 Fig 145 Burners and Combustion Chamber NT1000 ...
Page 133: ...NeoTherm LC Boilers and Water Heaters Page 129 Fig 146 Burners and Combustion Chamber NT1700 ...
Page 135: ...NeoTherm LC Boilers and Water Heaters Page 131 Fig 149 Burner Detail NT1700 ...
Page 136: ...LAARS Heating Systems Page 132 Fig 150 Electronic Components Fig 151 Condensate Trap NT1000 ...
Page 138: ...LAARS Heating Systems Page 134 This page intentionally left blank ...
Page 139: ...NeoTherm LC Boilers and Water Heaters Page 135 This page intentionally left blank ...