NeoTherm LC Boilers and Water Heaters
Page 3
manual includes two longer sections that will help
you to work with the control system:
•
Section 8 – “Using the Touch Screen and the
Gauges.”
This section will explain how to “Navigate”
through the Touch Screen : how to enter and
change values, and so on.
•
Section 9 – “Setup and Configuration”
The first part of this section includes a more
complete explanation of the Lead/Lag system.
The rest of the section includes detailed setup
instructions.
If you are not familiar with the control system, the
installation and setup process will go much more
smoothly if you read through these three sections
before beginning work.
1.3
Safety Notes
WARNING
Fire or Explosion Hazard
Improper configuration can cause fuel buildup and
explosion. Improper user operation may result in
property loss, severe physical injury, or death.
Any changes to safety-related configuration
parameters must only be done by experienced and/or
licensed burner/boiler operators and mechanics.
If any odor of gas is detected, or if the gas burner
does not appear to be functioning in a normal
manner,
close the main gas shutoff valve
. Do not
shut off the power switch. Contact your heating
contractor, gas company, or factory representative.
The NeoTherm LC Appliance is protected against
over-pressurization. A pressure relief valve is
included with each NeoTherm LC.
The inlet gas pressure to the appliance must not
exceed 13” W.C. (3.2 kPa).
All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54-
Latest Edition “National Fuel Gas Code” or 2) CSA
B149.1 “Natural Gas and Propane Installation Code”
and with the requirement of the local utility or other
authorities having jurisdiction. Such applicable
requirements take precedence over the general
instructions contained herein.
WARNING
Carbon Monoxide Hazard
Improper adjustment of the burners may lead to poor
combustion quality, increasing the amount of carbon
monoxide produced. Excessive carbon monoxide
levels may lead to personal injury or death.
WARNING
Electrical Shock Hazard
Electrical shock can cause severe injury, death or
property damage. Disconnect the power supply
before beginning installation or changing the
wiring to prevent electrical shock or damage to the
equipment. It may be necessary to turn off more than
one power supply disconnect.
All electrical wiring is to be done in accordance with
local codes, or in the absence of local codes, with:
1) The National Electrical Code ANSI/NFPA No.
70 - latest Edition, or 2) CSA STD. C22.1 “Canadian
Electrical Code - Part 1.” This appliance must be
electrically grounded in accordance with these
codes.
1.4
Model Identification
Consult the rating plate on the unit. The following
information describes the model number structure.
(1-2)
Model Series Designation
N T = NeoTherm LC
(3)
Usage
H = Hydronic
V = Volume Water
(4-7)
Size
1 0 0 0 = 1,000,000 BTU/hr input
1 7 0 0 = 1,700,000 BTU/hr input
(8)
Fuel
N = Natural Gas
P = LP Gas
(9)
Options Code
J = CSD1 Version
X = Standard Unit
(10)
Pump Options
X = No pump
(11)
Revision
1 = First version
Model Nomenclature
1 2 3
4 5 6
8
9
10
11
N T H
1
SERIES
N T
USAGE
H -
HYDRONIC
V -
VOLUME
WATER
SIZE
MBTU/h
1 0 0 0
1 7 0 0
FUEL
N -
NATURAL
P -
PROPANE
OPTIONS CODE
J
- CSD1
X -
STANDARD
PUMP OPTIONS
X -
NO PUMP
REVISION
1 -
FIRST
7
Summary of Contents for NTH1000
Page 4: ...LAARS Heating Systems ...
Page 11: ...NeoTherm LC Boilers and Water Heaters Page 7 Fig 6 Dimensions NT 1700 ...
Page 37: ...NeoTherm LC Boilers and Water Heaters Page 33 Fig 21 Ladder Diagram ...
Page 38: ...LAARS Heating Systems Page 34 Fig 22 Wiring Diagram ...
Page 39: ...NeoTherm LC Boilers and Water Heaters Page 35 ...
Page 51: ...NeoTherm LC Boilers and Water Heaters Page 47 Fig 51 Connection Terminals ...
Page 128: ...LAARS Heating Systems Page 124 Fig 140 Machine Frame NT1000 13 3 Parts Illustrations ...
Page 130: ...LAARS Heating Systems Page 126 Fig 143 Machine Frame NT1700 ...
Page 132: ...LAARS Heating Systems Page 128 Fig 145 Burners and Combustion Chamber NT1000 ...
Page 133: ...NeoTherm LC Boilers and Water Heaters Page 129 Fig 146 Burners and Combustion Chamber NT1700 ...
Page 135: ...NeoTherm LC Boilers and Water Heaters Page 131 Fig 149 Burner Detail NT1700 ...
Page 136: ...LAARS Heating Systems Page 132 Fig 150 Electronic Components Fig 151 Condensate Trap NT1000 ...
Page 138: ...LAARS Heating Systems Page 134 This page intentionally left blank ...
Page 139: ...NeoTherm LC Boilers and Water Heaters Page 135 This page intentionally left blank ...