Page 68
LAARS Heating Systems
11.2 Troubleshooting Table
This table includes a listing of the fault codes that may be displayed. Some of these can be corrected by
changing a parameter, while other conditions are more complicated, and will require a service technician.
The fi rst column lists the code number that will appear at the beginning of the Lockout or Hold message in
the orange bar at the bottom of the screen. The second column lists the text as it will appear on the Touch
Screen. The third column shows whether the condition will cause a Hold, or Lockout, or both. The fourth
column lists some suggestions for corrective action.
Code
Description
Lockout
or Hold
Procedure
1
Unconfi gured safety data
L
1. New device, complete device confi guration and
safety verifi cation.
2. If fault repeats, replace module
2
Waiting for safety
data verifi cation
L
1. Device in Confi guration mode and safety
parameters need verifi cation and a device needs
reset to complete verifi cation.
2. Confi guration ended without verifi cation, re enter
confi guration, verify safety parameters and reset
device to complete verifi cation.
3. If fault repeats, replace module.
3
Internal fault:
Hardware fault
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
4
Internal fault:
Safety Relay key feedback error
H
5
Internal fault:
Unstable power (DC DC) output
H
6
Internal fault:
Invalid processor clock
H
7
Internal fault:
Safety relay drive error
H
8
Internal fault:
Zero crossing not detected
H
9
Internal fault:
Flame bias out of range
H
10
Internal fault:
Invalid burner control state
L
11
Internal fault:
Invalid burner control state fl ag
L
12
Internal fault:
Safety relay drive cap short
H
13
Internal fault:
PII (Pre-Ignition Interlock) shorted
to ILK (Interlock)
H or L
15
Internal fault:
Safety relay test failed due to
feedback ON
L
Summary of Contents for NTH
Page 4: ...LAARS Heating Systems...
Page 13: ...Page 9 NEOTHERM Boilers and Water Heaters 38 1 2 98 8 3 4 22 7 1 2 19 64...
Page 30: ...Page 26 LAARS Heating Systems Figure 21 Hydronic Piping Single Boiler Zoning with Circulators...
Page 86: ...Page 82 LAARS Heating Systems Parts Illustration 1 Jacket Components...
Page 88: ...Page 84 LAARS Heating Systems Parts Illustration 4 Internal Components Sizes 750 850...
Page 90: ...Page 86 LAARS Heating Systems Parts Illustration 6 Gas Train Components Sizes 600 850...
Page 93: ...Page 89 NEOTHERM Boilers and Water Heaters Notes...
Page 94: ...Page 90 LAARS Heating Systems Notes...
Page 95: ...Page 91 NEOTHERM Boilers and Water Heaters Notes...