Mascot II Boilers and Water Heaters
Page 29
for established flame. If flame is sensed the control
enters "Run" to satisfy the demand. If flame is not
established the control enters a retry, starting from
step 2. If flame has not been established in the
appropriate number of retries the control will
lockout with a 109 error code.
7.
Call for heat complete
8.
Gas valve off
9.
Fan and pump over run times active to purge the
system
The sequence is the same for DHW or Central
Heat modes. Upon a call for Central Heat, the 3-way
valve will shift position, allowing boiler water to enter
the building's heating loop.
8.3 Modulation Control
The control uses a PID algorithm to adjust the
firing rate of the boiler as the control point is
approached. The goal of the control is to operate at a
minimum firing rate to match the load on the appliance.
The burner modulates to achieve the setpoint
temperature, away from the actual off point.
8.4 Pump Control
The boiler pump is active anytime there is a call
for heat applied to the control. When there is a central
heat call supplied the system pump relay is active. If
there is a DHW call supplied while the central heat call
is active the system pump turns off. This happens
because of domestic hot water priority, which forces the
control to satisfy the domestic water demand prior to the
hydronic demand. When the last heat demand is
satisfied the boiler pump enters an overrun time.
8.5 High Limit
The control uses a dual thermistor sensor to
monitor the Mascot II's maximum temperature. The
high limit sensor is installed in the outlet water. A dual
thermistor sensor is used, so that the two temperatures
can be monitored and compared to confirm accuracy.
The control will automatically reduce the firing of the
Mascot II to prevent the high limit from tripping. The
high limit setpoint is not adjustable.
8.6 Stack Temperature
The stack temperature is a dual thermistor sensor
and is limit rated. The control compares each of the
temperature readings to determine accuracy. The stack
sensor is used as a limiting feature to avoid excessive
temperatures in the venting.
8.7 Domestic Hot Water Temperature
The domestic hot water temperature sensor is used
to control DHW temperature. The DHW setpoint can be
adjusted through the USER menu structure.
DHW setpoint is displayed during DHW mode.
For LMH model, an aquastat will be used in lieu of a
sensor to control temperature of an indirect tank.
8.8 Lead Lag / Cascading
Lead Lag/Cascading allows multiple boilers to be
connected together and controlled from one common
sensor input. Up to 8 boilers can be connected together
in a single system. To setup Lead/Lag or cascading
operation there are several settings in the "setup" menu
structure that must be adjusted for the specific
installation, each is covered in the following sections.
8.8.1 Lead Lag Setpoint
The lead lag setpoint is set from the "user" menu
using the "LL" variable. This is the temperature the
boiler is attempting to maintain at the system sensor.
This setting doesn't control the boiler outlet
temperature, so the water temperature at the boiler outlet
may be much hotter than the system temperature
setpoint. Adjust the LL setpoint to the desired operating
temperature of the system.
8.8.2 Lead Lag Master/Slave Selection
In the SETUP menu structure, the "LL" menu
allows the lead lag system to be turned on and the boiler
to be configured as a master or slave control. In each
lead lag system there can only be one master control, so
proper selection is important to avoid operating issues.
To set the boiler to lead lag "master" operation the LL
menu should be set to "LDR". To set the boiler to slave,
"SLA" should be selected.
8.8.3 Lead Lag Address
The Lead Lag address must be set for each boiler
connected to the lead lag system. Each boiler must have
a unique address selected for the system to work
properly. Typically, the lead or master boiler should be
set to address one and the remaining boilers should be
set to values 2–8 depending upon how many boilers are
installed in the system.
8.8.4 Lead Lag Hysteresis
The lead lag system uses a hysteresis value set in
the setup menu, called, "HS". The hysteresis and
setpoint values control the on and off points of the
boiler. If the lead lag setpoint is adjusted to 120°F with
a hysteresis value of 5°F the boiler will turn off when
the water temperature reaches 125°F and will turn back
on when the water temperature reaches 115°F. Set the
hysteresis values to match the boiler to the system
operating characteristics. Setting this value correctly
will help reduce the chance of short cycling.
8.8.5 Lead Lag Base Load Setting
The lead lag system uses a base load setting that is
set through the "setup" menu called "bL". The base load
setting identifies the firing rate that the operating boiler
must achieve before the next boiler in the system is
allowed to operate. The default setting is 50% to avoid
short cycling and operating the boilers at higher, less
efficient, firing rates.
Summary of Contents for Mascot II
Page 6: ...LAARS Heating Systems Page 6 Figure 2 Location of Components...
Page 27: ...Mascot II Boilers and Water Heaters Page 27 Figure 22 Wiring Diagram...
Page 42: ...LAARS Heating Systems Page 42 Figure 28 Panel Assembly Door Top...
Page 43: ...Mascot II Boilers and Water Heaters Page 43 Figure 29 Panel Assembly Door Middle...
Page 44: ...LAARS Heating Systems Page 44 Figure 30 Panel Assembly Door Bottom...
Page 45: ...Mascot II Boilers and Water Heaters Page 45 Figure 31 Base Jacket Assembly...
Page 46: ...LAARS Heating Systems Page 46 Figure 32 Heat Exchanger Cabinet Fan...
Page 47: ...Mascot II Boilers and Water Heaters Page 47 Figure 33 Heat Exchanger Burner Components...
Page 48: ...LAARS Heating Systems Page 48 Figure 34 Pump Assembly Components...
Page 49: ...Mascot II Boilers and Water Heaters Page 49 Figure 35 Plumbing Components...
Page 50: ...LAARS Heating Systems Page 50...