Mascot II Boilers and Water Heaters
Page 25
SECTION 7.
Electrical Connections
WARNING
The appliance must be electrically grounded in
accordance with the requirements of the authority
having jurisdiction or, in the absence of such
requirements, with the latest edition of the National
Electrical Code, ANSI/NFPA 70, in the U.S. and with
latest edition of CSA C22.1 Canadian Electrical Code,
Part 1, in Canada. Do not rely on the gas or water piping
to ground the metal parts of the boiler. Plastic pipe or
dielectric unions may isolate the boiler electrically.
Service and maintenance personnel, who work on or
around the boiler, may be standing on wet floors and
could be electrocuted by an ungrounded boiler.
Electrocution can result in severe injury or death.
Single pole switches, including those of safety
controls and protective devices must not be wired in a
grounded line.
All electrical connections are made on the terminal
blocks that are located inside the control panel.
NOTE:
All internal electrical components have been
prewired. No attempt should be made to connect
electrical wires to any other location except the terminal
blocks.
Wiring connections are shown in
Figures 21-22.
Important Note:
DO NOT MAKE/BREAK MASCOT II
LINE VOLTAGE TO SIGNAL CALL FOR HEAT. A “call
for heat / end call for heat” MUST be connected to the
field interlock terminals. Some Mascot II components
are designed to have constant voltage during normal
operation. If the Mascot II's supply voltage is toggled as
a call for heat signal, premature failure of these
components may result.
If using remote 4-20mA control, Mascot II does not
recognize 4mA as a signal to shut off. If the call for heat
is not connected between the field interlock terminals,
Mascot II will remain in low fire when it sees 4mA as a
modulating signal.
Caution
Mascot II supply voltage must not be disengaged,
except for service or isolation, or unless otherwise
instructed by procedures outlined in this manual. To
signal a call for heat, use the 24V field-interlock, as
shown in the wiring diagram(s).
7.1 Main Power
Plug power cord into a non-switched 115V
electrical outlet with 15A circuit protection. FLA is 2A.
There is an internal 10A breaker to protect internal
system components.
7.2 Pump Connections
Mascot II energizes the integral boiler pump (and
three-way valve if central heat) upon a call for heat.
Once the call for heat is satisfied the pump will remain
on for the defined pump overrun time.
NOTE:
System pump contacts are dry contacts.
Appropriate voltage must be supplied to the System
pump for proper operation.
System pump connections are located in the
control panel (
see Figure 20
). The system pump
contacts are rated for 120Vac, 7.4 amps. To use the
contacts, power must be supplied on one terminal with
the other terminal wired to the pump or a relay
controlling the pump.
7.3 24Vac Transformer with Circuit Breaker
24Vac is supplied by a transformer mounted
behind the upper door. All 24Vac power is supplied
through a 2A circuit breaker located behind middle door.
7.4 Central Heat - Call for Heat
Connect the Call for Heat to terminals #1 and #2
(connections labeled "T-T or interlock").
7.5 Outdoor Air Temperature Sensor
Connect the outdoor air temperature sensor to
connections labeled "Outdoor temp sensor." The outdoor
air temperature sensor is used for warm weather shutdown
and outdoor reset.
7.6 Domestic Hot Water Connection
For LMH and indirect water heater, connect
aquastat for remote sensor to terminals 7 & 8 (see
Figures 20 and 22
).
7.7 System Sensor
(lead lag/cascading operation only)
Connect the system sensor to connections labeled
"system sensor."
7.8 External Control Connections
Connect 4-20mA signals from external controls or
building automation systems. When making the
connections, follow the polarity designations shown on
the label.
7.9 Lead Lag / Cascading Wiring
Connections
Connect each boiler in the cascade system together
by daisy chaining each control from Modbus port 1
(MB1) of the first boiler to the second and so on. This
can be done using 22awg or thicker shielded twisted pair
wire with drain. Two twisted pairs or three conductors
are needed.
a.
To daisy-chain the boilers connect a wire from Modbus
Summary of Contents for Mascot II
Page 6: ...LAARS Heating Systems Page 6 Figure 2 Location of Components...
Page 27: ...Mascot II Boilers and Water Heaters Page 27 Figure 22 Wiring Diagram...
Page 42: ...LAARS Heating Systems Page 42 Figure 28 Panel Assembly Door Top...
Page 43: ...Mascot II Boilers and Water Heaters Page 43 Figure 29 Panel Assembly Door Middle...
Page 44: ...LAARS Heating Systems Page 44 Figure 30 Panel Assembly Door Bottom...
Page 45: ...Mascot II Boilers and Water Heaters Page 45 Figure 31 Base Jacket Assembly...
Page 46: ...LAARS Heating Systems Page 46 Figure 32 Heat Exchanger Cabinet Fan...
Page 47: ...Mascot II Boilers and Water Heaters Page 47 Figure 33 Heat Exchanger Burner Components...
Page 48: ...LAARS Heating Systems Page 48 Figure 34 Pump Assembly Components...
Page 49: ...Mascot II Boilers and Water Heaters Page 49 Figure 35 Plumbing Components...
Page 50: ...LAARS Heating Systems Page 50...