background image

LAARS Heating Systems

Page 36

ignitor assembly in the reverse order if the old assembly
is determined defective. Replace gasket if necessary.

11.2.4  Flame Sensor

The flame sensor is a single rod system. To replace

the flame sensor electrode, shut off the 120 Volt power
supply to the boiler. Turn off all manual gas valves
connecting the boiler to the main gas supply line.
Remove the front door of the boiler to gain access to the
flame sensor electrode. Remove the flame sensor wire
from the electrode. Remove the two bolts fastening the
electrode to the burner doors. Remove and replace the
old flame sensor gasket. Reinstall a new flame sensor
electrode in the reverse order if the old electrode is
determined defective.

 Caution

Igniters and sensors get hot and

can cause burns or injury.

11.2.5  Blower

The combustion air blower is a high-pressure

centrifugal blower with a variable speed motor. Speed
of the motor is determined by the control logic. 120
Volts remain on to the blower at all times. If a blower
change is required, turn off the 120 Volt power and gas
supply to the unit. Take the front panel off. Disconnect
the 120 Volt and control signal connections from the
blower. Disconnect the bolts connecting the venturi to
the blower housing. Disconnect the fan outlet bolts from
the burner door blower arm. If the fan is determined to
be defective replace the existing fan with a new one
reversing the steps above. Make sure to install all of the
required O-rings and gaskets between the blower arm
and the blower and blower face and venturi flange.

11.2.6  Heat Exchanger Coils

Black carbon soot buildup on the external surfaces

of the heat exchanger is caused by one or more of the
following; incomplete combustion, combustion air
problems, venting problems and heater short cycling.
Soot buildup or other debris on the heat exchanger may
restrict the flue passages.

If black carbon soot buildup on the heat exchanger

is suspected, disconnect electrical supply to the unit,
and turn off the gas supply by closing the manual gas
valve on the unit. Access the heat exchanger through the
burner door at the front of the boiler, and inspect the
tubing using a flashlight. If there is a buildup of black
carbon soot or other debris on the heat exchanger, clean
per the following:

 Caution

Black carbon soot buildup on a dirty heat exchanger
can be ignited by a random spark or flame. To
prevent this from happening, dampen the soot
deposits with a wet brush or fine water spray before
servicing the heat exchanger.

1.

Shut off the 120 Volt power supply to the boiler

2.

Turn off all manual gas valves connecting the

boiler to the main gas supply line.

3.

Remove the four bolts connecting the blower
flange to the burner door arm.

4.

Remove the nuts located on the outside diameter
of the burner door to the heat exchanger.

5.

Remove the burner door/burner assembly from the
heat exchanger.

6.

Disconnect the condensate drain line.

7.

Attach a longer hose to drain and run to a bucket.

8.

Clean the heat exchanger by brushing light
accumulations of soot and debris. Use a brush with
soft bristle (non metal) to avoid damaging the
surface of the heat exchanger tubes.

9.

Once the tubes have been brushed clean rinse the
tubes and combustion chamber with a small
amount of water to rinse all of the debris out of the
bottom of the flue collector and into the longer
condensate trap line, which is being diverted into a
separate container.

NOTE: The Warranty does not cover damage caused
by lack of required maintenance, lack of water flow,
or improper operating practices.

 

WARNING

Failure to rinse the debris from the heat exchanger
and temporary drain line may lead to clogged
condensate lines, traps and neutralizers. Condensate
pumps (if used) may also be damaged from the
debris left behind, possibly causing property damage.

11.

Install all components removed in the reverse
order to place the appliance back in operation.
Make sure all gaskets are in place as components
are installed. Replace any damaged gaskets. Do
NOT reuse damaged gaskets.

12.

Place the appliance in operation according to

Section 10

 checking all gas connections for leaks.

Confirm all fasteners are tight.

11.2.7  Gas Conversion

Mascot II units can be converted from natural to

propane gas or from propane to natural gas easily in the
field. If a gas conversion is performed, the unit must be
identified with the appropriate gas labels and a
conversion sticker to allow technicians performing
maintenance in the future to properly identify the gas
type of the appliance. These stickers are included with
the boiler during shipment.

 WARNING

This conversion shall be installed by a qualified
service agency in accordance with the
manufacturer's instructions and all applicable codes
and requirements of the authority having jurisdiction.
If the information in these instructions is not followed
exactly, a fire, an explosion or production of carbon
monoxide may result causing property damage,
personal injury or loss of life.  The qualified service
agency is responsible for the proper and complete

Summary of Contents for Mascot II

Page 1: ...monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void the warranty AVERTISSEMENT Assurez vous de bien suivres les instr...

Page 2: ...ating System Pump Capacity 17 SECTION 6 Water Connections 6 1 Central Heat System Piping 17 6 2 Cold Water Make Up 17 6 3 Freeze Protection 18 6 4 Suggested Piping Schematics 19 6 5 Recognized Chemica...

Page 3: ...Operating the Burner and Set Up 32 10 2 1 Burner Operation 32 10 2 2 Boiler Setup and Adjustment 33 10 3 Shutting Down Mascot II 33 10 4 To Restart Mascot II 33 SECTION 11 Maintenance 11 1 System Main...

Page 4: ...he PRV should be installed prior to filling the system Refer to Figures 1 and 2 for PRV locations IMPORTANT The inlet gas pressure to the appliance must not exceed 13 W C 3 2kPa All installations must...

Page 5: ...sponsible for shortages and damage to the shipment whether visible or concealed 1 5 Unpacking The Mascot II is shipped in a single crate with the following standard components packed with the applianc...

Page 6: ...LAARS Heating Systems Page 6 Figure 2 Location of Components...

Page 7: ...Water Heaters Page 7 Figure 3 Dimensional Drawing Cond Hydronic DHW 2nd Gas Hydronic DHW 2nd Outlet Return Inlet Return Supply Supply Outlet Supply 3 4 3 4 1 2 3 4 1 2 3 4 1 2 3 4 PVC copper NPT copp...

Page 8: ...ertified to ULC S636 Intake air pipe must be PVC or CPVC that complies with ANSI ASTM D1785 F441 ABS that complies with ANSI ASTM D1527 or galvanized material Installer must comply fully with manufact...

Page 9: ...ll bracket are purposely offset NOTE Mascot II models include 16 on center mounting holes on upper rear of boiler jacket These holes are not identified on the mounting template If mounting conditions...

Page 10: ...of the combustion air intake pipe Maximum linear pipe length allowed is shown in Table 2 Subtract 5 allowable linear ft 1 5m for every elbow used The connection for the intake air pipe is at the top...

Page 11: ...el or otherwise must be certified to this ULC standard Appropriate selection of vent material is very important for proper performance and safe operation of the Mascot II The flue temperature of the M...

Page 12: ...e a nuisance or hazard 3 Locate the vent terminal so that vent gases cannot be drawn into air conditioning system inlets 4 Locate the vent terminal so that vent gases cannot enter the building through...

Page 13: ...4 3 feet 91 cm J Clearance to nonmechanical air supply Direct vent only 12 30cm 80 285 36 91cm inlet to building or the combustion air inlet 399 850 Other than Direct vent 4 ft 1 2m below 36 inches 91...

Page 14: ...shall be the responsibility of the property owner to secure the services of qualified licensed professionals for installation of hard wired carbon monoxide detec tors a In the event that the side wal...

Page 15: ...um speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so the appliance will operate...

Page 16: ...ing plate Mascot II will function properly without the use of high altitude modification at elevations up to 10 000 feet 3050 m 2 The maximum inlet gas pressure must not exceed 13 W C 3 2kPa The minim...

Page 17: ...toff valves where required by code Suggested piping diagrams are shown in Figures 12 through 19 These diagrams are meant only as a guide Components required by local codes must be properly installed M...

Page 18: ...a boiler is subjected to freezing conditions and the boiler is not able to fire and or the water is not able to circulate there is a risk of freezing in the boiler or in the pipes in the system When w...

Page 19: ...itable for use in the Mascot II Please refer to the manufacturers instructions for proper selection and application 1 Sentinel Performance Solutions Group 2 Hercules Chemical Company 3 Dow Chemical Co...

Page 20: ...3 42 38 15 33 31 28 Table 8 DHW and Pump Performance Data Caution Scalding Risk Laars recommends the use of a thermostatic mixing valve at domestic hot water outlet boiler location to reduce potential...

Page 21: ...Mascot II Boilers and Water Heaters Page 21 Figure 16 Hydronic Piping Multi boilers for large homes with long multiple baseboard zones Installer to provide DHW anti scald thermostatic mixing valve...

Page 22: ...LAARS Heating Systems Page 22 Figure 17 Hydronic Piping Multi boilers for large homes with long multiple radiant zones Installer to provide DHW anti scald thermostatic mixing valve...

Page 23: ...Mascot II Boilers and Water Heaters Page 23 Figure 18 Hydronic Piping Heating zones piped with zone pumps Installer to provide DHW anti scald thermostatic mixing valve...

Page 24: ...LAARS Heating Systems Page 24 Figure 19 Hydronic Piping Heating zones piped with zone valves Installer to provide DHW anti scald thermostatic mixing valve...

Page 25: ...he 24V field interlock as shown in the wiring diagram s 7 1 Main Power Plug power cord into a non switched 115V electrical outlet with 15A circuit protection FLA is 2A There is an internal 10A breaker...

Page 26: ...teps until all Modbus port 1 terminal A connections are wired d Repeat the above steps for Modbus port 1 terminal B and C connections to complete the wiring e Connect the drain wire from the twisted p...

Page 27: ...Mascot II Boilers and Water Heaters Page 27 Figure 22 Wiring Diagram...

Page 28: ...in Tables 9 11 Once in a particular menu structure navigation consists of pressing the next button to scroll from item to item and then pressing the up and down arrows to change values Once the value...

Page 29: ...to control temperature of an indirect tank 8 8 Lead Lag Cascading Lead Lag Cascading allows multiple boilers to be connected together and controlled from one common sensor input Up to 8 boilers can b...

Page 30: ...Reset Outdoor reset varies the control point setpoint based on the actual outdoor temperature The reset function works as shown in Figure 24 When the outdoor air temperature reaches the high outdoor t...

Page 31: ...then the boilers will simultaneously drop their firing rate If when reaching the point where both boilers drop toward their minimum firing rate 20 then the first slave will drop out Slave1 will remai...

Page 32: ...energize for pre purge then the ignition sequence starts After all safety devices are verified the gas valve opens If ignition doesn t occur turn off the Mascot II check that there is SECTION 10 Oper...

Page 33: ...can be forced to low fire to allow for easier setup Refer to Section 8 1 Table 11 for instructions on how to access the forced rate menu CO2 readings should be between the values shown in Table 13 If...

Page 34: ...LAARS Heating Systems Page 34 GAS TYPE HIGH FIRE CO2 LOW FIRE CO2 Natural 9 0 9 0 Propane 10 0 10 0 Table 13 CO2 Range Figure 25 Adjustment Screws and Settings for CO2...

Page 35: ...e Pump 11 2 1 Burner Check the burner for debris Remove the blower arm assembly to access the burner Remove the 4 bolts connecting the blower to the arm see Figure 32 Remove the 5 bolts which hold the...

Page 36: ...e soot deposits with a wet brush or fine water spray before servicing the heat exchanger 1 Shut off the 120 Volt power supply to the boiler 2 Turn off all manual gas valves connecting the boiler to th...

Page 37: ...um input CO2 Any high fire adjustment may affect low fire settings Screws for adjustment are shown in Figure 26 7 Reinstall front cover SECTION 12 Trouble Shooting 12 1 Sequence of Operation Mascot II...

Page 38: ...92 Outlet sensor fault 93 DHW sensor fault Faulty sensor or wiring Check wiring replace sensor condition can be 95 Stack sensor fault caused by short 96 OAT temperature sensor fault Faulty outdoor ai...

Page 39: ...values min 12 C 22 F to a difference greater than 22 F 12 C 255 CH setpoint minus ODR Increase Outdoor water min water temperature was temperature min and max too small min 12 C 22 F values to a diff...

Page 40: ...ral Information To order or purchase parts for the LAARS Mascot II contact your nearest LAARS dealer or distributor If they cannot supply you with what you need contact Customer Service see back cover...

Page 41: ...1 4 npt E2337500 8O Exchanger heat plate 8P Tie cable 14 3 4 long x 0 31 wide heat stabilized F2029100 8Q Flow switch water E2337400 8R Pipe tailpiece 1 npt M x 3 4 tube cu 12H4023 8S O ring 120 1 ID...

Page 42: ...LAARS Heating Systems Page 42 Figure 28 Panel Assembly Door Top...

Page 43: ...Mascot II Boilers and Water Heaters Page 43 Figure 29 Panel Assembly Door Middle...

Page 44: ...LAARS Heating Systems Page 44 Figure 30 Panel Assembly Door Bottom...

Page 45: ...Mascot II Boilers and Water Heaters Page 45 Figure 31 Base Jacket Assembly...

Page 46: ...LAARS Heating Systems Page 46 Figure 32 Heat Exchanger Cabinet Fan...

Page 47: ...Mascot II Boilers and Water Heaters Page 47 Figure 33 Heat Exchanger Burner Components...

Page 48: ...LAARS Heating Systems Page 48 Figure 34 Pump Assembly Components...

Page 49: ...Mascot II Boilers and Water Heaters Page 49 Figure 35 Plumbing Components...

Page 50: ...LAARS Heating Systems Page 50...

Page 51: ...Mascot II Boilers and Water Heaters Page 51...

Page 52: ...Fax 603 335 3355 Applications Engineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A Laars Heating Systems 1111 Document 1230A Dime...

Reviews: