background image

LAARS Heating Systems

Page 16

SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY

UNDILUTED PROPANE

NOMINAL PIPE SIZE 

@

 11" W.C. INLET AND 0.5" W.C. PRESSURE DROP

SIZE

1/2"

3/4"

LENGTH      MAXIMUM CAPACITY IN THOUSANDS OF BTU PER HOUR

20

200

418

40

137

287

60

110

231

80

94

197

100

84

175

NOTES:

 1. Follow all local and national LP gas codes for line sizing and

equipment requirements.  2. Verify that inlet gas pressure remains between
4 and 13 inches of water column before and during operation.

Source: ANSI Z223.1-80 National Fuel Gas Code.

Table 6D.

SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY NATURAL GAS

NOMINAL PIPE SIZE 

@

 0.30" W.C. PRESSURE DROP

LENGTH

1/2"

3/4"

FT

CUBIC FEET OF GAS PER HOUR

20

92

190

40

130

60

105

80

90

100

Table 6C.

MASCOT II NATURAL GAS REQUIRED

SIZE

CU FT / HR.

125

125

TO SIZE PIPING:

Measure linear distance from meter outlet to last boiler. Add total
input of all boilers and divide by 1000 to obtain cu ft / hr required.
Add total equivalent length of fittings used according to Table 6B.
Align total length (pipe and fittings) on left side column of Table 6C
with highest cubic feet of gas required.

Notes:

Consult and confirm with Applicable Fuel Gas Code before beginning
work. Verify gas inlet pressure is between 4 and 13 in W.C. before
starting boiler.

Table 6A.

SECTION 4.
Gas Supply and Piping

4.1 Gas Supply and Piping

Gas piping should be supported by suitable

hangers or floor stands, not the appliance.

Review the following instructions before

proceeding with the installation.

1.

Verify that the appliance is fitted for the proper type of
gas by checking the rating plate. Mascot II will
function properly without the use of high altitude
modification at elevations up to 10,000 feet (3050 m).

2.

The maximum inlet gas pressure must not exceed
13" W.C. (3.2kPa). The minimum inlet gas
pressure is 4" W.C. (1.0kPa).

3.

Refer to 

Tables 6A, 6B, 6C and 6D

 to size piping.

4.

Run gas supply line in accordance with all
applicable codes.

5.

Locate and install manual shutoff valves in
accordance with state and local requirements.

6.

A sediment trap must be provided upstream of the
gas controls.

7.

All threaded joints should be coated with piping
compound resistant to action of liquefied
petroleum gas.

8.

The appliance and its individual shutoff valve
must be disconnected from the gas supply piping
during any pressure testing of that system at test
pressures in excess of 1/2 PSIG (3.45kPa).

9.

The unit must be isolated from the gas supply
system by closing its individual manual shutoff
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than
1/2 PSIG (3.45kPa).

10.

The appliance and its gas connection must be leak
tested before placing it in operation.

11.

Purge all air from gas lines.

 WARNING:

Open flame can cause gas to ignite and result in
property damage, severe injury, or loss of life.

NOTE

: The Mascot II appliance and all other gas

appliances sharing the gas supply line must be firing at
maximum capacity to properly measure the inlet supply
pressure. The pressure can be measured at the supply
pressure port on the gas valve. Low gas pressure could
be an indication of an undersized gas meter, undersized
gas supply lines and/or an obstructed gas supply line.

EQUIVALENT LENGTHS OF STRAIGHT PIPE FOR TYPICAL SCH 40 FITTINGS

NOMINAL PIPE SIZE

FITTING

1/2"

3/4"

1"

LINEAR FEET

90° ELBOW

3.6

4.4

5.2

TEE

4.2

5.3

6.6

Table 6B.

Summary of Contents for Mascot II

Page 1: ...monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void the warranty AVERTISSEMENT Assurez vous de bien suivres les instr...

Page 2: ...ating System Pump Capacity 17 SECTION 6 Water Connections 6 1 Central Heat System Piping 17 6 2 Cold Water Make Up 17 6 3 Freeze Protection 18 6 4 Suggested Piping Schematics 19 6 5 Recognized Chemica...

Page 3: ...Operating the Burner and Set Up 32 10 2 1 Burner Operation 32 10 2 2 Boiler Setup and Adjustment 33 10 3 Shutting Down Mascot II 33 10 4 To Restart Mascot II 33 SECTION 11 Maintenance 11 1 System Main...

Page 4: ...he PRV should be installed prior to filling the system Refer to Figures 1 and 2 for PRV locations IMPORTANT The inlet gas pressure to the appliance must not exceed 13 W C 3 2kPa All installations must...

Page 5: ...sponsible for shortages and damage to the shipment whether visible or concealed 1 5 Unpacking The Mascot II is shipped in a single crate with the following standard components packed with the applianc...

Page 6: ...LAARS Heating Systems Page 6 Figure 2 Location of Components...

Page 7: ...Water Heaters Page 7 Figure 3 Dimensional Drawing Cond Hydronic DHW 2nd Gas Hydronic DHW 2nd Outlet Return Inlet Return Supply Supply Outlet Supply 3 4 3 4 1 2 3 4 1 2 3 4 1 2 3 4 PVC copper NPT copp...

Page 8: ...ertified to ULC S636 Intake air pipe must be PVC or CPVC that complies with ANSI ASTM D1785 F441 ABS that complies with ANSI ASTM D1527 or galvanized material Installer must comply fully with manufact...

Page 9: ...ll bracket are purposely offset NOTE Mascot II models include 16 on center mounting holes on upper rear of boiler jacket These holes are not identified on the mounting template If mounting conditions...

Page 10: ...of the combustion air intake pipe Maximum linear pipe length allowed is shown in Table 2 Subtract 5 allowable linear ft 1 5m for every elbow used The connection for the intake air pipe is at the top...

Page 11: ...el or otherwise must be certified to this ULC standard Appropriate selection of vent material is very important for proper performance and safe operation of the Mascot II The flue temperature of the M...

Page 12: ...e a nuisance or hazard 3 Locate the vent terminal so that vent gases cannot be drawn into air conditioning system inlets 4 Locate the vent terminal so that vent gases cannot enter the building through...

Page 13: ...4 3 feet 91 cm J Clearance to nonmechanical air supply Direct vent only 12 30cm 80 285 36 91cm inlet to building or the combustion air inlet 399 850 Other than Direct vent 4 ft 1 2m below 36 inches 91...

Page 14: ...shall be the responsibility of the property owner to secure the services of qualified licensed professionals for installation of hard wired carbon monoxide detec tors a In the event that the side wal...

Page 15: ...um speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so the appliance will operate...

Page 16: ...ing plate Mascot II will function properly without the use of high altitude modification at elevations up to 10 000 feet 3050 m 2 The maximum inlet gas pressure must not exceed 13 W C 3 2kPa The minim...

Page 17: ...toff valves where required by code Suggested piping diagrams are shown in Figures 12 through 19 These diagrams are meant only as a guide Components required by local codes must be properly installed M...

Page 18: ...a boiler is subjected to freezing conditions and the boiler is not able to fire and or the water is not able to circulate there is a risk of freezing in the boiler or in the pipes in the system When w...

Page 19: ...itable for use in the Mascot II Please refer to the manufacturers instructions for proper selection and application 1 Sentinel Performance Solutions Group 2 Hercules Chemical Company 3 Dow Chemical Co...

Page 20: ...3 42 38 15 33 31 28 Table 8 DHW and Pump Performance Data Caution Scalding Risk Laars recommends the use of a thermostatic mixing valve at domestic hot water outlet boiler location to reduce potential...

Page 21: ...Mascot II Boilers and Water Heaters Page 21 Figure 16 Hydronic Piping Multi boilers for large homes with long multiple baseboard zones Installer to provide DHW anti scald thermostatic mixing valve...

Page 22: ...LAARS Heating Systems Page 22 Figure 17 Hydronic Piping Multi boilers for large homes with long multiple radiant zones Installer to provide DHW anti scald thermostatic mixing valve...

Page 23: ...Mascot II Boilers and Water Heaters Page 23 Figure 18 Hydronic Piping Heating zones piped with zone pumps Installer to provide DHW anti scald thermostatic mixing valve...

Page 24: ...LAARS Heating Systems Page 24 Figure 19 Hydronic Piping Heating zones piped with zone valves Installer to provide DHW anti scald thermostatic mixing valve...

Page 25: ...he 24V field interlock as shown in the wiring diagram s 7 1 Main Power Plug power cord into a non switched 115V electrical outlet with 15A circuit protection FLA is 2A There is an internal 10A breaker...

Page 26: ...teps until all Modbus port 1 terminal A connections are wired d Repeat the above steps for Modbus port 1 terminal B and C connections to complete the wiring e Connect the drain wire from the twisted p...

Page 27: ...Mascot II Boilers and Water Heaters Page 27 Figure 22 Wiring Diagram...

Page 28: ...in Tables 9 11 Once in a particular menu structure navigation consists of pressing the next button to scroll from item to item and then pressing the up and down arrows to change values Once the value...

Page 29: ...to control temperature of an indirect tank 8 8 Lead Lag Cascading Lead Lag Cascading allows multiple boilers to be connected together and controlled from one common sensor input Up to 8 boilers can b...

Page 30: ...Reset Outdoor reset varies the control point setpoint based on the actual outdoor temperature The reset function works as shown in Figure 24 When the outdoor air temperature reaches the high outdoor t...

Page 31: ...then the boilers will simultaneously drop their firing rate If when reaching the point where both boilers drop toward their minimum firing rate 20 then the first slave will drop out Slave1 will remai...

Page 32: ...energize for pre purge then the ignition sequence starts After all safety devices are verified the gas valve opens If ignition doesn t occur turn off the Mascot II check that there is SECTION 10 Oper...

Page 33: ...can be forced to low fire to allow for easier setup Refer to Section 8 1 Table 11 for instructions on how to access the forced rate menu CO2 readings should be between the values shown in Table 13 If...

Page 34: ...LAARS Heating Systems Page 34 GAS TYPE HIGH FIRE CO2 LOW FIRE CO2 Natural 9 0 9 0 Propane 10 0 10 0 Table 13 CO2 Range Figure 25 Adjustment Screws and Settings for CO2...

Page 35: ...e Pump 11 2 1 Burner Check the burner for debris Remove the blower arm assembly to access the burner Remove the 4 bolts connecting the blower to the arm see Figure 32 Remove the 5 bolts which hold the...

Page 36: ...e soot deposits with a wet brush or fine water spray before servicing the heat exchanger 1 Shut off the 120 Volt power supply to the boiler 2 Turn off all manual gas valves connecting the boiler to th...

Page 37: ...um input CO2 Any high fire adjustment may affect low fire settings Screws for adjustment are shown in Figure 26 7 Reinstall front cover SECTION 12 Trouble Shooting 12 1 Sequence of Operation Mascot II...

Page 38: ...92 Outlet sensor fault 93 DHW sensor fault Faulty sensor or wiring Check wiring replace sensor condition can be 95 Stack sensor fault caused by short 96 OAT temperature sensor fault Faulty outdoor ai...

Page 39: ...values min 12 C 22 F to a difference greater than 22 F 12 C 255 CH setpoint minus ODR Increase Outdoor water min water temperature was temperature min and max too small min 12 C 22 F values to a diff...

Page 40: ...ral Information To order or purchase parts for the LAARS Mascot II contact your nearest LAARS dealer or distributor If they cannot supply you with what you need contact Customer Service see back cover...

Page 41: ...1 4 npt E2337500 8O Exchanger heat plate 8P Tie cable 14 3 4 long x 0 31 wide heat stabilized F2029100 8Q Flow switch water E2337400 8R Pipe tailpiece 1 npt M x 3 4 tube cu 12H4023 8S O ring 120 1 ID...

Page 42: ...LAARS Heating Systems Page 42 Figure 28 Panel Assembly Door Top...

Page 43: ...Mascot II Boilers and Water Heaters Page 43 Figure 29 Panel Assembly Door Middle...

Page 44: ...LAARS Heating Systems Page 44 Figure 30 Panel Assembly Door Bottom...

Page 45: ...Mascot II Boilers and Water Heaters Page 45 Figure 31 Base Jacket Assembly...

Page 46: ...LAARS Heating Systems Page 46 Figure 32 Heat Exchanger Cabinet Fan...

Page 47: ...Mascot II Boilers and Water Heaters Page 47 Figure 33 Heat Exchanger Burner Components...

Page 48: ...LAARS Heating Systems Page 48 Figure 34 Pump Assembly Components...

Page 49: ...Mascot II Boilers and Water Heaters Page 49 Figure 35 Plumbing Components...

Page 50: ...LAARS Heating Systems Page 50...

Page 51: ...Mascot II Boilers and Water Heaters Page 51...

Page 52: ...Fax 603 335 3355 Applications Engineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A Laars Heating Systems 1111 Document 1230A Dime...

Reviews: