ENGLIsH
Press the T2 button to access the
TECHNICAL SETTINGS
menu.
WARNING
: the parameters in the technical menu should never be modified. Such operation must only be performed by an
Authorised La NORDICA S.p.A. Service Centre
. La NORDICA S.p.A. is not liable for product malfunctions due to the
parameters in the technical menu being modified without authorisation.
HOT WATER TEMPERATURE
The water temperature is shown on the display.
In the event of excess water temperature the device warns the user with an indicator light and an audible signal; the latter may be
enabled or disabled via the BUZZER function in the MENU.
See EXCESS TEMPERATURE ALARM.
NOTE
: The circulating pump activation temperature is a factory setting.
FROST PROTECTION
The frost protection function is always active on the device and acts by starting the pump when the temperature measured by the
probe is less than 5°C / 41°F (fixed threshold).
When the frost protection function is active, LED 1 Danger comes on and the message “FROST PROTECTION” is shown on the
display.
ANTI-BLOCKAGE
The ANTI-BLOCKAGE function automatically starts the pumps connected to the controller for 30 seconds after an extended period
of inactivity (~96 hours without power being disconnected).
When the ANTI-BLOCKAGE function is activated, the display shows the message “ANTI-BLOCKAGE”.
WARNING
: to ensure the ANTI-BLOCKAGE function is not disabled, always leave the digital controller connected to the
power supply (the display shows OFF).
EXCESS TEMPERATURE ALARM
When the temperature measured by the water probe exceeds 87°C / 188.6°F (fixed threshold set), this alarm is activated, starting
the circulating pumps.
When the alarm is activated, LED 1 Danger comes on and the message “EXCESS TEMPERATURE” is shown on the display.
FAULTY PROBE ALARM
When a probe fault occurs, this alarm is activated, starting the circulating pumps.
When the alarm is activated, LED 1 Danger comes on and the message “FAULTY PROBE” is shown on the display.
AIR VENT
Air inside the water circuit causes noise and may damage the circulating pumps. The presence of air may occur following installation
of the product or any other work on the water circuit.
Vent any air inside the system by operating the digital controller as follows:
•
the water in the system must be at room temperature;
•
with the digital controller OFF, press buttons
T2
and
T3
together. The display shows the message “AIR VENT”.
EXTRA FUNCTIONS
The sub-menus are accessed from the
TECHNICAL SETTINGS
menu.
The boiler and puffer settings are accessed by pressing T4 in the
SYSTEM
menu. Press T4 again to scroll the parameters. Press T2
and T3 to modify the parameters. Press T4 again to confirm the changes and move on to the next parameter in the menu until you
return to the SYSTEM menu.
3-WAY VALVE
The 3-way valve is activated by the controller (if present and connected to the controller, as described in Chapter
7.3
) with the device
ON and when the temperature detected by probe
I1
exceeds the value set for THRESHOLD OUT1=60°C (PR01) and the boiler is in
the demand status. It is disabled when the temperature detected by probe
I1
drops below the value set for THRESHOLD OUT1=60°C
less the hysteresis value DELTA OUT1=5°C (PR02), i.e. below 55 °C or when required. (See diagrams
6
).
BOILER ACTIVE
Activate the boiler by setting parameter PR08=ON and connecting probe
I3
Optional (L= 2 metres) as described in Chapter
7.3
.
The boiler enters the request status (if activated PR08=ON) with the device ON until the temperature detected by probe
I3
reaches
the SET BOILER MAX=60°C (PR09) value, at which point the request is fulfilled. The boiler returns to the request status when the
temperature detected by probe
I3
drops below the SET BOILER MIN=30°C (PR10) value. (See diagrams
4
and
6
).
PUFFER ACTIVE
Activate the puffer by setting parameter PR11=ON and connecting probe
I2
Optional (L= 2 metres) as described in Chapter
7.3
.
The puffer enters request status with the device ON until the difference between the temperature detected by
I1
and that detected by
probe
I2
is greater than the DT ON=7°C (PR12) value. When the same difference drops below the DT OFF=5°C (PR13) value, the
puffer exits from the request status. (See diagrams
5
and
6
).
13