26
LANGUAGE
BUZZER
ON - OFF
DISPLAY
10 - 100%
TECHNICAL
SETTINGS
SETTINGS FACTORY
CODE 44
SET DEGREES
°C- F
ITALIANO
ENGLISH
FRANCAIS
ESPANOL
DEUTSH
TEST OUTPUTS
SYSTEM
PR01
CIRCULATOR
1 Threshold OUT 1
(55- 65°C)
Default = Heating device 60°C
PR02
CIRCULATOR
1 Delta OUT 1
(1 - 5°C)
Default = 5°C
TEST OUT
1
TEST OUT
2
TEST OUT
3
STATUS Stove
I1
= xx°C
(H
2
O probe)
I2
= xx°C
(
PUFFER
probe)
I3
= xx°C
(
BOILER
probe)
I4
= On / Off
(Flow switch)
PR11
BOILER
( On / Off )
PR09 SET BOILER Max
( 47 - 70°C )
PR10 SET BOILER Min
( 30 - 46°C )
PR11
PUFFER
(
On / Off
)
PR12 thermal differential
to PUFFER On (5 - 12°C) Default = 7°C
PR13 thermal differential to PUFFER Off (3 - 8°C) Default = 5°C
PR03
CIRCULATOR
2 Threshold OUT 2
(65 - 75°C)
Default = Heating device 70°C
PR04
CIRCULATOR
2
Delta OUT 2
(1 - 5°C)
Default = 5°C
PR05 ANTIFREEZE Threshold
(2 - 10°C)
Default = 5°C
PRODUCT
CODE 33
5.2. FLOW CHART - MENU
5.3. EXTRA FUNCTIONS
The
TECHNICAL SETTINGS
menu can be used to:
Press key T4 to enter the
SYSTEM menu
. Press the T4 key to enter the
BOILER
and
PUFFER sub-menu
, use buttons T2 / T3. Press T4
to confirm the selection.
5.3.1. THREE-WAYS VALVE
The
three-ways valve
is activated when the controller is “ON” , when the BOILER is ON (PR08=ON) and the temperature measured by
the
I1
water temperature probe exceeds the selected one, default OUT1=60°C (PR01) delta OUT1=5°C (PR02).
.
5.3.2. BOILER Activated
The
BOILER
is activated when the controller is “ON” .
The BOILER is ON (PR08=ON) when the temperature measured by the
I3
water temperature probe (OPTIONAL / L= 2 meters) exceeds
the selected one, SET BOILER MIN=30°C (PR10) MAX=60°C (PR09).
, and
5.3.3. PUFFER Activated
The
PUFFER
is activated when the controller is “ON” .
The PUFFER is ON (PR11=ON) when the difference between the temperature, measured by the
I2
water temperature probe (OPTIONAL /