The exhaust cap and the two air
turbulation strips are factory installed.
See Service Parts Schematic for
replacement.
Assemble the tee, nipple, and cap to the nipple at the
gas inlet of the heater. See Fig. 8. Use a wrench to
hold the pipe nipple when installing the sediment trap.
Tighten securely. The sediment trap assembly must
always be mounted in a vertical position. Check all
connections for gas leaks using approved gas leak
detectors.
Air Turbulation Strips
& Exhaust Cap
Sediment Trap Assembly
FIG. 8
NIPPLE
TEE
NIPPLE
CAP
TO GAS CONTROL VALVE INLET
Hanging Chains
2X4 Support
Ceiling Joists
Eyebolt
5 ft. on center
4 ft. on center
S-Hooks
Exhaust Vent
Clamp
FIG. 6
DESPERDICIOS
SENSOR IN PROXIMITY
TO AN INSIDE WATER LINE
DE 12"
A 18"
Temperature Sensor Location
FIG. 7
WATER LINES
INSIDE WATER LINES
5 FT.
LITTER
SENSOR
12-18 IN.
ABOVE LITTER
WATER LINE
HEATER
SENSOR LOCATED DIRECTLY
ABOVE INSIDE WATER LINE AND
12-18 IN. ABOVE LITTER
FEED LINE
FEED LINE