Oval-U 100
Radiant Tube Heaters
www.lbwhite.com
Owner’s Manual • Oval-U 100
Radiant Tube Heaters
4
Specifications
UT100
Maximum Input per Hour BTU/H
100,000
Fuel Consumption per Hour (Max.)
LPG (lbs.)
4.6
NG (cu. ft.)
100
Gas supply pressure acceptacle
for the purpose of input adjustment
(in.W.C.)
MAX.
LPG
13.5
NG
MIN.
LPG
11.0
NG
7.0
Burner manifold pressure (in.W.C.)
LPG
10.0
NG
4.0
Ventilation air required to support
combustion
140 CFM
Motor Characteristics
1/30 H.P., 3020 RPM, CW Rotation
Electrical supply (Volts/Hz/Phase)
120/60/1
Amp draw
Starting
1.16
Continuous
Operation
1.02
Minimum safe distances of heater
from nearest combustible materials
(ft.) See Fig. 1 on page 5.
Top
0.5
Sides
3.0
Discharge End
3.0
Below radiant tubes
6.0
Temperature
sensor location
See Fig. 7 on page 13 of the
owner’s manual.