Troubleshooting Electrical Problems
5-14
KVAL 979-2 Operation/Service Manual
Start Light OFF
If the Start light remains unlit, push in the Start button
and hold it in while a second person checks for volt-
age between #2 and #75. If there is 110 VAC, replace
the ACR relay. If there is no voltage while the button
is held in, check the wiring.
First isolate the power supply. Check between DC+
and DC- for 24VDC. If no DC voltage, disconnect
the output (V+ and V-) wires from the 24VDC
power supply and check for DC voltage where
those wires were disconnected.
If no voltage:
Check the input side for 110 VAC. If no 110 VAC, check the fuse. If there is 110
VAC and no 24VDC, replace the 24VDC Power Supply.
If there is 24VDC:
Reconnect the output wires to the 24VDC power supply.
Trace the output wire to the DC terminal block.
Disconnect all (+ 24V positive) wires from the + DC from the DC terminal block
except the + output wire from the + 24VDC power supply.
Check for +24VDC at between any –DC and +DC terminal on the DC Terminal
block.
Reinstall the (+ 24V positive) wires one by one, checking for +24VDC after
installing each. If at any point no voltage is found trace the last reinstalled wire and
check for shorts.
Input 110 VAC
Output 24 VDC
24VDC Light OFF
Summary of Contents for 979-2
Page 4: ...KVAL 979 2 Operation Service Manual ...
Page 8: ...979 2 Miter Trim Saw System ...
Page 23: ...Getting Help from KVAL 1 15 KVAL 979 2 Operation Service Manual Page Intentionally Left Blank ...
Page 25: ...Safety Sign Off Sheet 1 17 KVAL 979 2 Operation Service Manual ...
Page 60: ...Notes ...
Page 64: ...System IT Administration 3 4 KVAL 979 2 Operation Service Manual ...
Page 86: ...Mechanical Adjustments 4 22 KVAL 979 2 Operation Service Manual ...
Page 105: ...Notes ...
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......