Manual
Kuhse Gateway Module
KGM - KEA
HB-KGM-KEA_EN Version 01
Date: 23rd. May 2017
Page 64 of 75
8.3.2
Counter values KEA2xx
DW
Counter value
Dimension
Value
DW 88
Operating hours MSW
h
65536
DW 90
Operating hours LSW
h
1
DW 92
Start counter MSW
-
65536
DW 94
Start counter LSW
-
1
DW 96
Reserve MSW
-
-
DW 98
Reserve LSW
-
-
DW 100 Reserve MSW
-
-
DW 102 Reserve LSW
-
-
8.3.3
Connection status to KEA 2xx
DW
Value
DW 104 H-Byte: Reserve
L-Byte: Data traffic (0=OK, 1 = disrupted)
8.3.4
Commands to KEA 2xx
DW
Command and parameter
Value
DW 00 Command #1: Target value from ZLT
$243C
DW 02 Parameter #1a: Power specification
0 -
1100‰
DW 04 Parameter #1b: Release target value from ZLT
$0100 ($0000 = no release)
DW 06 Repeat parameter #1b:
$0100
DW 08 Command #2: Command from ZLT
$2850
DW 10 Parameter #2: Bit commands (com. 8 - 1 / 16 - 9)
e.g. Central control system (ZLT)
command 1: $0100
DW 12 Reserve
DW 14 Reserve
To ensure that the commands will be accepted by the KEA, the value cited in
the table for the respective command must be transmitted in the data word. The
transmission of command values that are not stipulated
(other than zero) can result in undesired reactions by the KEA!