Manual
Kuhse Gateway Module
KGM - KEA
HB-KGM-KEA_EN Version 01
Date: 23rd. May 2017
Page 55 of 75
8.2
PROFINET
PROFINET .GSDML file: GSDML-V2.31-Kuhse-KNG-YYYYMMDD.xml
The .GSDML file as well as a Siemens example project can be found
under
www.kuhse.de/download/software.html
.
Direction
Data
Number
Input bytes
Output bytes
From KGM
Fault messages
4 word input
0 - 7
-
Status messages
4 word input
8 - 15
-
Analogue values I
16 word input
16 - 47
-
Analogue values II
16 word input
48 - 79
-
Analogue values III
4 word input
80 - 87
-
Counter values
8 word input
88 - 103
-
Status values
1 word input
104 - 105
-
To the
KGM
Transmission data
8 word output
0 - 15
Notation of individual bits within a data word:
Bit 15 = MSB ("left" in the data word), Bit 00 = LSB
H-Byte
L-Byte
Bit
no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Example notation, Siemens:
H-Byte
L-Byte
Bit
no.
0.7
0.6 0.5 0.4 0.3 0.2 0.1 0.0 1.7 1.6 1.5 1.4 1.3 1.2 1.1
1.0
Some analogue values, e.g. network current and network power, are only
valid if they are recorded by the automated system. This is dependent on
the KEA type and can be looked up in the operating instructions for the
KEA.
The address of the data is stipulated in bytes (Siemens notation),
e.g. Data word DW 02 comprises byte 02 and byte 03.