Manual
Kuhse Gateway Module
KGM - KEA
HB-KGM-KEA_EN Version 01
Date: 23rd. May 2017
Page 52 of 75
8.1.1.3
Analogue values KEA2xx (FC03)
Register Analogue value
Dimension Value
47101 Mains voltage L1
V
1
47102 Mains voltage L2
V
1
47103 Mains voltage L3
V
1
47104 Mains frequency
Hz
0.01
47105 Reserve
-
-
47106 Reserve
-
-
47107 Reserve
-
-
47108 Reserve
-
-
47109 Generator voltage L1
V
1
47110 Generator voltage L2
V
1
47111 Generator voltage L3
V
1
47112 Generator frequency
Hz
0.01
47113 Generator current L1
A
1
47114 Generator current L2
A
1
47115 Generator current L3
A
1
47116 Generator effective power
kW
0.1
47117 Battery voltage
V
0.1
47118 Speed
rpm
1
47119 Analogue value 1
Temperatures without,
oil pressure with decimal
place
47120 Analogue value 2
47121 Analogue value 3
47122 Analogue value 4
47123 Reserve
-
-
47124 Reserve
-
-
47125 Reserve
-
-
47126 Reserve
-
-
47127 Cos phi generator L1
-
0.01
47128 Cos phi generator L2
-
0.01
47129 Cos phi generator L3
-
0.01
47130 Generator apparent power
kVA
1
47131 Reserve
-
-
47132 Generator load
%
1
47133 Reserve
-
-
47134 Reserve
-
-
47135 Reserve
-
-
47136 Reserve
-
-