Manual
Kuhse Gateway Module
KGM - KEA
HB-KGM-KEA_EN Version 01
Date: 23rd. May 2017
Page 60 of 75
8.3
PROFIBUS
PROFIBUS .GSD file: HIL_0C99.GSD
The .GSD file can be found under
www.kuhse.de/download/software.html
.
Direction
Data
Number
Input bytes
Output bytes
From KGM
Fault messages
4 word input
0 - 7
-
Status messages
4 word input
8 - 15
-
Analogue values I
16 word input
16 - 47
-
Analogue values II
16 word input
48 - 79
-
Analogue values III
4 word input
80 - 87
-
Counter values
8 word input
88 - 103
-
Status values
1 word input
104 - 105
-
To the KGM Transmission data
8 word output
0 - 15
Direction
Data
Number
Input bytes
Output bytes
From KGM
Digital inputs KGM 1 word
106 - 107
-
To the KGM
Digital outputs
KGM
1 word
-
16 - 17
Notation of individual bits within a data word:
Bit 15 = MSB ("left" in the data word), Bit 00 = LSB
H-Byte
L-Byte
Bit
no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Example notation, Siemens:
H-Byte
L-Byte
Bit
no.
0.7
0.6 0.5 0.4 0.3 0.2 0.1 0.0 1.7 1.6 1.5 1.4 1.3 1.2 1.1
1.0
Some analogue values, e.g. network current and network power, are only valid
if they are recorded by the automated system. This is dependent on the
KEA type and can be looked up in the operating instructions for the KEA.
The address of the data is stipulated in bytes (Siemens notation),
e.g. Data word DW 02 comprises byte 02 and byte 03.