Object 2101h: Node address
This Object can be used to change the node address via software. The default value is set to 10h
(CANLift Default).
Data content:
Range of values 1 ...127 or 1..7Fh
Default
setting:
10h
The
node number 0
is reserved and may not be used by any node. The resulting node
numbers lie in the range
1...7Fh
hexadecimal or (1...127)
The acceptance of a new node number only becomes effective when the encoder is
rebooted (Reset/Power-on) or by means of an
NMT Reset Node
command. All other
settings within the object table are however retained.
Object 2102h: CANbus Termination
T
his Object can be used to set the bus termination via software.By default the value is
set to 1
,
which means that the hardware setting for the bus termination has priority.
Range of values 0..1
Default
setting:
1
Please note that when software termination is selected, then the hardware settings are
non-operative and vice versa.
Object 2103h: Firmware Flashversion
This object is used to display the current firmware version as a 16-bit hexadecimal value.
This value serves to verify that the device is to the latest revision.
Range of values: to FFFFh
Example:
4FA6h
current
firmware