- 10 -
4.1 Run.
The run chapter contains all parameters which is significance for the different functions in “Run”.
4.1.1 Set temperature.
In this chapter you can find all parameters concerned the set temperature while operating.
4.1.1.1 Set temperature °C
Setting of the boiler’s flow temperature
Please select:
Menu / Run / Set temp / Set temp °C
The desired set temperature can be set minimum 70°C and maximum 95 °C
4.1.1.2 Go pause temp +°C
Setting of how many degrees the temperature is set above the boilers set temperature before the boiler
goes in pause mode.
Please select:
Menu/ / Run / Set temp / +°C
It can be set from minimum 1°C but no maximum.
4.1.1.3 Back to run mode -°C
Setting of how many degrees the temperature is allowed to run below set temperature before you desire
the boiler to start again.
Please select:
Menu / Run / Set temp / Back to run mode -°C
It can be set from minimum 1°C but no maximum °C.
4.1.1.4 Maximum output %
Which output do you desire the boiler to operate with no matter how delayed the boiler is.
Please select:
Menu / Run / Set temp / Max output %
It can be set from minimum 1 % but no maximum.