19
SMARTRONIC MA
Alternating current
Direct current
220 V
127 V
48 V
24 V
115 V
48 V
24 V
Control of pure resistive load and
static loads with isolation by
optocouplers
5
5
5
5
0,6
2
5
Control of static loads with transfor-
mer isolation
2,5
3
4
4
0,3
1
3
Control of electromagnetic loads
2,5
3
4
4
0,04
0,15
0,6
V - 3 End stop connection
Proximity
detectors
Mechanical
microswitches
SMARTRONIC MA R1310 terminal block
Technical characteristics of mechanical microswitches (Crouzet ref.: 83181)
- Box: thermoplastic polyester loaded with glass fibre,
Material:
-
Button: polyamide UL 94 V0 loaded with glass fibre,
- Contact: nickel- plated silver.
Rating:
- Heat transmission power: 6 A,
-
Cut-off power according to IEC 947.5.1.
Endurance, lifetime:
- electrical:
- under I = 5A : 10
5
cycles,
- under I = 1A : 10
6
cycles,
- under I = 0,2A : 10
7
cycles
- mechanical:
3.10
7
cycles
Acceptable maximal current in A
Technical characteristics of proximity detectors (IFM ref.: XC0035)
Housing material:
Polybutylenetherephtalate
Power supply voltage:
5 to 36 VDC
Maximum output current:
inrush:
200 mA
continuous:
200 mA
Minimum output current:
4 mA
Maximum voltage drop:
4,6 V
Residual current:
0,8 mA
Maximum switching frequency:
2 kHz
Operation indication
By LED