SMARTRONIC MA
VII - 5 - 7 Displaying positioning data
The SMARTRONIC MA allows read only access to the values required for its positioning, via the ”OPERATION”
menu.
- ”In CURRENT” indicates in mA the setpoint current in the 4- 20mA input loop
- ”SETPOINT” indicates as a % the valve positioning setpoint.
- ”POSITION” indicates as a % the instantaneous value of the valve position.
- ”SETPOINT” indicates as a % the error between the setpoint and the instantaneous position of the
valve.
Access to these parameters:
>main menu
>1.operation
1.OPERATION >
<OK>
<ESC>
+
1.In CURRENT
xx.xx mA
+
-
>1.operation
2.SETPOINT
xxx.x%
--
+
-
>1.operation
3.POSITION
xxx.x %
+
-
>1.operation
4.DEVIATION
xxx.x %
VII - 5 - 8 Displaying HART version - addressing data
The ”INFO” menu provides access to the embedded software version number and the compatible HART
version number of the product.
This menu can also be used to read and configure the product address in a HART network (POLL addr).
Access to these parameters:
>main menu
>4.info
4.INFO >
<OK>
<ESC>
1.Soft vX.X
+
-
>4.info
2.Hart vX.X
--
+
+
-
>4.info
>4>3.poll
>4>3.poll add
3.POLL addr >
<OK>
<ESC>
SET ADDR
X X
<OK>
<ESC>
VALID ?
<OK> or <ESC>
VII - 5 - 9 HART compatibility
This positioner is HART compatible. The HART protocol can be used to communicate with the instrumentation
via a Pocket, computer or programmable unit. It is therefore easy to configure the instrument, save this
configuration, perform a product diagnosis, display the measured values, and much more
(see §VIII - 1 - 1 HART parameter). Communication is carried out by frequency modulation (FSK type) injected
on the 4- 20 mA setpoint signal.
To connect a HART console, refer to paragraph V - 5.