5 Installation at Site
26 of 74
HPK-L
1136.8/15-EN
CAUTION
Aggressive flushing liquid and pickling agent
Damage to the pump!
▷
Match the cleaning operation mode and duration of flushing and pickling to
the casing materials and seal materials used.
5.3.2 Permissible forces and moments at the pump nozzles
[+]
F
y
F
z
F
x
F
x
F
z
F
y
F
x
F
z
F
y
M
y
M
z
M
x
Forces and moments at the pump nozzles
The permissible resultant forces have
been determined according to:
The data on forces and moments apply to static piping loads only. If the limits are
exceeded, they must be checked and verified.
If a computerised strength analysis is required, values are available on request only.
The values are only applicable if the pump is installed on a completely grouted
baseplate and bolted to a rigid and level foundation.
Table 10:
Forces and moments at the pump nozzles
Sizes
Suction nozzle
Discharge nozzle
Suction nozzle
Discharge nozzle
[N]
[N]
[Nm]
[Nm]
F
x
F
y
F
z
F
res
F
x
F
yTens
+ F
yCompr
-
F
z
F
res
M
x
M
y
M
z
M
x
M
y
M
z
25-160
1050
700
850
1100
500
350
650
450
700
550
450
300
400
300
200
25-200
1050
700
850
1100
500
350
650
450
700
550
450
300
400
300
200
32-125
1350
900
1100
1400
700
450
850
550
900
700
550
350
450
350
250
32-160
1350
900
1100
1400
700
450
850
550
900
700
550
350
450
350
250
32-200
1350
900
1100
1400
700
450
850
550
900
700
550
350
450
350
250
32-250
1350
900
1100
1400
700
450
850
550
900
700
550
350
450
350
250
40-160
1750
1150
1400
1800
850
550
1100
700
1100
1150
850
600
550
450
300
40-200
1750
1150
1400
1800
850
550
1100
700
1100
1150
850
600
550
450
300
40-250
1750
1150
1400
1800
850
550
1100
700
1100
1150
850
600
550
450
300
40-315
1750
1150
1400
1800
850
550
1100
700
1100
1150
850
600
550
450
300
50-160
2150
1400
1700
2200
1100
700
1350
900
1400
1450 1100
750
700
550
350
50-200
2150
1400
1700
2200
1100
700
1350
900
1400
1450 1100
750
700
550
350
50-250
2150
1400
1700
2200
1100
700
1350
900
1400
1450 1100
750
700
550
350
50-315
2150
1400
1700
2200
1100
700
1350
900
1400
1450 1100
750
700
550
350
65-160
2700
1750
2150
2750
1400
900
1750
1150
1800
2000 1500 1000 1150
850
600
65-200
2700
1750
2150
2750
1400
900
1750
1150
1800
2000 1500 1000 1150
850
600
65-250
2700
1750
2150
2750
1400
900
1750
1150
1800
2000 1500 1000 1150
850
600
65-315
2700
1750
2150
2750
1400
900
1750
1150
1800
2000 1500 1000 1150
850
600
80-160
3700
2400
2950
3800
1700
1100
2150
1400
2200
2750 2100 1400 1450 1100
750
80-200
3700
2400
2950
3800
1700
1100
2150
1400
2200
2750 2100 1400 1450 1100
750
80-250
3700
2400
2950
3800
1700
1100
2150
1400
2200
2750 2100 1400 1450 1100
750
Summary of Contents for HPK-L
Page 1: ...Thermal Oil Hot Water Pump HPK L Installation Operating Manual ...
Page 72: ......
Page 73: ......