![KSB Ama-Drainer-Box Operating Manual Download Page 22](http://html.mh-extra.com/html/ksb/ama-drainer-box/ama-drainer-box_operating-manual_2006544022.webp)
5 Installation at Site
22 of 72
Ama-Drainer-Box
1
710.01
90
720.04
60
Ⓐ
Fig. 7:
Fitting the discharge line of a single-pump system; setting the installation
dimension; dimensions in [mm]
1
Fitting direction (from outside to inside)
CAUTION
Discharge pipe not aligned, installation dimension not complied with
Risk of fracture due to impermissible stresses and strains at the connections!
Submersible motor pump cannot be installed in the collecting tank!
▷
Observe the alignment of the discharge pipe and the installation dimension
(see illustration).
Discharge line of dual-pump units Z2 U - DN 50
Y-pipe 715 can be connected using one of two options:
▪
External thread G 2
or, after removing the threaded section,
▪
glued nozzle with an outside diameter of 63 mm
1.
Fit profile seal 410.01.
2.
Fit Y-pipe 715.
If the discharge line is connected via a glued joint, remove the threaded section
of the Y-pipe in the area marked
Ⓐ
using a saw or angle grinder; debur the
pipe end.
3.
Insert the Y-pipe into the profile seal from the inside. Apply a sufficient amount
of lubricant to the pipe end before inserting it.
4.
Align the Y-pipe horizontally. Always observe the installation dimension.
5.
Connect the discharge line provided at the site.
Summary of Contents for Ama-Drainer-Box
Page 1: ...Automatic Waste Water Lifting Unit Ama Drainer Box Installation Operating Manual ...
Page 64: ...9 Related Documents 64 of 72 Ama Drainer Box ...
Page 69: ......
Page 70: ......
Page 71: ......