ELECTRICAL INSTALLATION
3
3.5
Connecting Flow Sensor to the Flow Computer
The Flow Sensor UFS-V also has to be connected to the I/O-rack of the Flow Computer UFP-V.
This is the PT100 connection which is connected in the Flow Sensor UFS-V to the PT100 (body
temperature) and in the I/O-rack to the MTL5073 module (A1) as shown below. This connection
has to be made with a shielded 4-wire cable (not supplied). In the Flow Sensor UFS-V and the
I/O-rack (Flow Computer UFP-V) this cable has to be connected in such way that the shield is
connected to the shield connectors. The cable has to be connected according to the table below.
Connector X2 UFS-
V
Wire
Connector MTL5073 module
5 1
1
7 3
3
6 2
4
8 4
5
Overview I/O-rack (Flow Computer UFP-V) front side
Module A1 ( I/O-rack Flow Computer UFP-V )