8. Boiler operation and maintenance
Use the main switch to deactivate the boiler and
wait until the boiler cools down - min. 1 hour before
maintenance (boiler cleaning).
8.A Burner operation guidelines:
Normal daily boiler operation:
³
check correct operation of system components: burner, control
system
³
check water level on a pressure gauge
³
check fuel level and quality and fuel feed system operation
³
check hydraulic joints leak tightness
³
keep the boiler room clean and tidy.
In case of any performance issues, remove the faulty devices or contact
an Authorised Service Centre to arrange a repair or an adjustment.
8.B Inspection scope and schedule
a) Monthly
³
check system water pressure
³
check safety valve operation
³
check control and safety device operation
³
check tightness of all connectors and joints
³
check balanced ventilation system
b) Minor inspection(every 6 months)
³
check rope seal and gaskets,
³
check boiler door thermal insulation,
³
check safety devices (safety valve, safety temperature limiter
STB etc.),
³
check flue gas (in case of a significant increase in flue gas tem-
perature, clean the combustion section of a boiler).
c) Major inspection(every 12 months)
³
check rope seal and gaskets,
³
check boiler door and cleanout cover thermal insulation,
³
check safety devices (safety valve, safety temperature limiter
STB etc.)
³
check flue gas
³
clean combustion section of the boiler
³
check thermal insulation of the boiler
³
check and adjust burner, adjust control system settings.
After a long boiler/burner standstill, the residual oxygen in boiler water
and the oxygen from the air mixed with a carbonic acid have highly
corrosive properties. Take any precautions necessary after a boiler
standstill for over a week.
Periodically remove the soot, sludge and ash from the combustion
chamber, the flue tubes and the grate. Clean the boiler as required, at
least every 2 weeks. Remove the ash as required.
8.C Maintenance
a) Boiler, burner, fuel feed system - mechanical
The regular and correct maintenance of the boiler is a precondition
of a correct and reliable operation and low fuel consumption of the
system. Contact an Authorised Service Centre at least once a year
and after every boiler standstill to arrange an inspection.
Heating system maintenance procedure:
³
deactivate the boiler (system) (stop mode)
³
wait for a complete stop and allow to cool
³
reduce the boiler temperature to the level allowing safe mainte-
nance
³
open boiler door
³
clean combustion chamber and all flues and check the rope se-
als in the boiler doors (replace if necessary)
³
check and clean burner (remove if necessary)–clean motor and
fan external surfaces (especially vanes)
³
close the boiler door with burner
³
remove the cover
³
clean the combustion products from the rear section of the boiler
³
check cover gasket quality (rope seals) and remove as required
³
close the rear boiler cleanout
³
check smoke duct condition and gas tightness
³
check installation and operation of the boiler sensors
³
check installation and operation of the fuel feed system
³
feeder gear motor
³
fuel feed ducts leak tightness and flow capacity
Summary of Contents for Mini Bio
Page 1: ......
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 46: ......
Page 48: ......
Page 86: ......
Page 88: ......
Page 126: ......
Page 127: ...Twin Bio PLV 09 13 Twin Bio PLV 09 13 R U PN EN303 5 2 0 1 2 PN EN30 3 5 2 0 1 2...
Page 128: ......
Page 130: ......
Page 154: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 154 6 154 ON 6...
Page 155: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 155 7 155 7...
Page 165: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 165 13 165 a STB STB...
Page 166: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 166 13 166 a...
Page 168: ......
Page 170: ......
Page 208: ......
Page 210: ......
Page 247: ......
Page 248: ......