65
Mini Bio
and
Mini Bio Luxury
User Manual - ENGV 08.15
Experts in heating
5.
Design
guide
l
ines
Fig. Boiler location in the boiler room - dimension diagram
5.B Boiler room requirements
a) Boiler foundation min.0.05 m
Boiler foundation requirements:
³
the foundation must protrude over the boiler room floor
³
the foundation edges must be secured with steel angle sections
b) Boiler room floor
Boiler room floor requirements:
³
the boiler room must be made of non-flammable materials,
resistant to extreme temperature changes and impact
³
the floor must descend in the well direction
c) Boiler room ventilation
Boiler room ventilation requirements:
³
do not use mechanical ventilation system in the room with solid
fuel furnace if the combustion air is supplied directly from the
room and the flue gas is discharged gravitationally via a duct
from the device
³
the boiler room must be fitted with a ventilation duct with a cross
section of at least 50% of the flue cross sectional area, min.
20x20 cm
³
the boiler room must be fitted with a ventilation duct with a cross
section of at least 25% of the flue cross sectional area with the
outlet under the boiler room ceiling
³
the outlet duct cross section must be min. 14x14 cm
³
the vents must be made of non-flammable materials
5.C Hydraulic system requirements
³
the hydraulic system must be made in accordance with the good
building practices, relevant standards and regulations, and the
design input
³
the boiler may operate in a sealed heating system (sealed
diaphragm tank) provided that the boiler supply and return line is
fitted with a dual action relief valve
³
a pressure reducer must be installed with a relief valve to avoid
safety valve opening in case of a rapid increase in boiler water
pressure
³
an expansion tank must be installed in the highest point of the
heating system and protected against frost
³
the expansion tank should be installed at the boiler return
³
to guarantee proper working conditions and failure free boiler
operation, ensure a minimum temperature at the boiler return
by installing the boiler pump with a mixing valve (boiler mixing
system)*
³
a temperature sensor of the system protecting against exceeding
permissible temperatures must be installed directly on the boiler
³
the boiler is compatible with water as a medium conforming to
the water quality requirements.
* Water temperature at the boiler return must be min.
45°C to prevent boiler corrosion as a result of undesirable
and excessive flue gas condensation in the boiler.
The boiler circulation pump must be fitted with a control
valve. The pump output must be approx. 40÷50%
of the nominal water flow through the boiler. The boiler
circuit design must guarantee the difference
in temperature between the supply and the return
of max. 15°C.
CAUTION!
The boiler pump must be installed between two
cut-off valves. To protect the pump against high
pressure difference between the suction and discharge:
´TY^_LWW_SPMZTWP][`X[L__SP^d^_PX]P_`]YP^[PNTLWWd
in systems with high water capacity, where the discharge
pressure is very high)
´[]Z_PN__SPMZTWP][`X[L__SP^`N_TZYLRLTY^_
low
pressure
Summary of Contents for Mini Bio
Page 1: ......
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 46: ......
Page 48: ......
Page 86: ......
Page 88: ......
Page 126: ......
Page 127: ...Twin Bio PLV 09 13 Twin Bio PLV 09 13 R U PN EN303 5 2 0 1 2 PN EN30 3 5 2 0 1 2...
Page 128: ......
Page 130: ......
Page 154: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 154 6 154 ON 6...
Page 155: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 155 7 155 7...
Page 165: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 165 13 165 a STB STB...
Page 166: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 166 13 166 a...
Page 168: ......
Page 170: ......
Page 208: ......
Page 210: ......
Page 247: ......
Page 248: ......