11002347AA
date of change: 20.08.2014
Page: 15/19
Group
]
dF
(parameter of defrosting control)
[refers to Pr2]
[defrost cycle „disables“ Pr1]
Par.
Description
Range
fac-
tory
set-
ting
cooling
hot-
gas
defrost
ing
cooling
recircu-
lated air
defrost-
ing
cooling
neutral
zone
heating
hot-gas
defrost-
ing
cooling
neutral zone
heating
recirculated
air defrost-
ing
d.dt
Defrosting mode:
EL = electrical defrost cycle
if defrost cycle is released and starts, then
defrosting (dEF) on / compressor (OUT) off
(compressor can not be activated via Pr1)
ın = defrost cycles by hot air/cycle reversal
if defrost cycle is released and starts, then
defrosting (dEF) on / compressor (OUT) on
FdE = defrost cycle by recirculated air (fans)
if defrost cycle is released and stars, then
defrosting (dEF) off / compressor (OUT) off
fan always on
EL – ın
– FdE
ın
ın
FdE
ın
FdE
d.dı
Defrost interval
Minimum duration between two defrost cycles (dEF
off)
of = Switching-off the defrosting
oF ÷
99.5
hrs.min
1.30
1.30
1.30
1.30
1.30
d.dE
Maximum duration of a defrost cycle (dEF on)
(duration of defrosting, if not interrupted by Pr2
[d.tE, d.tS])
0.01 ÷
99.5
min.se
c
15.0
15.00
15.00
15.00
15.00
d.tE
Defrost limit temperature
(if the temperature Pr2 is higher than the adjusted
value d.tE, then dEF will be switched off)
- 58 ÷
302
°C/°F
8.0
8.0
8.0
8.0
8.0
d.tS
Defrost switch-on temperature
(temperature Pr2 must fall below d.tS, before d.tE
engages again)
- 58 ÷
302
°C/°F
2.0
2.0
2.0
2.0
2.0
d.dC
Timer mode defrost intervals („timer for d.dı, dEF
off)
rt = total “unit on“ – time counts
ct = „OUT on“ – time counts
cS = defrost cycle after evaporator off
(dEF on / d.dE-time, consider d.dı = oF)
rt - ct -
cS
rt
rt
rt
rt
rt
d.td
Compressor delays after defrost cycle (dripping-off)
compressor remains switched-off, LED OUT is
blinking until time d.td is running out.
oF ÷
99.5
min.se
c
1
1
oF
1
oF
d.Sd
Defrost cycle when switching-on
on - oF
of
of
of
of
of
d.dL
Display lock during defrost cycle
oF = no lock
on = lock on temperature measurement
Lb = lock, in display appears
“dEF” (in defrost cycle, dEF = on)
“PdF” (after defrost cycle, dEF = off, )
on - oF
- Lb
Lb
Lb
Lb
Lb
Lb