Group
]
ts
(parameter of keyboard configuration)
Par.
Description
Range
factory
setting
t.Fb
Operating mode button DOWN
oF = no function
1 = control auxiliary outlet
2 = manual defrost cycle
3 = activate setpoint
4 = switching-on/-off (stand-by)
indication of
-
Operating hours
-
Service hours
Example:
Service-hours counter
if 200 was programmed
then 200 x 10 = 2000
oF / 1 / 2 / 3 / 4
0…999 h x 10
0…999 h x 10
oF
t.UF
Operating mode button U
4= switching on/-off (stand-by)
oF / 1 / 2 / 3 / 4
4
t.PP
Password for access to operating parameter
oF ÷ 999
213
t.Sr Service-hours counter
If the programmed value is exceeded, „SEr“ will be
indicated in the display for approx. 5 seconds
This will be indicated with every switching-on of the
FR4, as long as the current value is > than the pro-
grammed value
Example:
if 200 was programmed
then 200 x 10 = 2000
oF ÷ 999 x 10
2000
t.rS Reset service-hours counter
By enter of „password „–181“ (minus 181)“ the ser-
vice-hours counter is reset to „0“.
If you enter the wrong password, the display returns
to normal indication and the current value of the ser-
vice-hours counter is conserved.
REMARK:
The password „-181“ is hard-coded.
-999 ÷ 999
0