EB-60X Installation & Service Manual |
Wiring
MASTER BDS4
SLAVE BDS5
CONNECTOR C1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CONNECTOR C1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
TC3
A-96170 CABLE
ASSEMBLY
- DIFF HI
- DIFF LO
HI
LO
TACH
SPEED COMMAND
INPUT: PINN 11
POSITIVE WITH
RESPECT TO PIN 1
WILL CAUSE MASTER
TO ROTATE
CLOCKWISE VIEWING
FROM SHAFT END.
TO REVERSE:
INTERCHANGE PIN 11
AND PIN 1 OF
CONNECTOR C1 ON
THE MASTER UNIT.
CONNECTION SHOWN IS FOR MASTER
AND SLAVE TO ROTATE IN SAME
DIRECTION. TO ENABLE MASTER AND
SLAVE TO ROTATE IN OPPOSITE
DIRECTION: INTERCHANGE PIN 11 AND
PIN 1 OF CONNECTOR C1 ON THE
SLAVE UNIT.
System Setup
1. The master unit requires a master (M) type compensation card – designated (i.e. BDS4-
230J/X0XA2M). The slave requires a slave(s) type compensation card – designated (i.e.
BDS4-230J/X0XA2S).
2. For proper load sharing between the master and slave units, the following adjustment
must be made on the slave unit (the stability and command scale pots now function as
torque gain adjustments):
•
Adjust the stability pot fully counter-clockwise.
•
Adjust the command scale pot fully clockwise
•
Adjust the current limit pot fully clockwise
•
Under load conditions, the load sharing may be improved slightly by comparing each
unit’s current monitor signal:
−
To increase load on the slave unit, adjust its stability pot clockwise
−
To decrease load on the slave unit, adjust its command scale pot counter-
clockwise.