Controller Accessories
Many functions that required optional accessories with
the M340+ controller are integrated into the
Decision-Maker
r
MPAC 1500 controller operation. For
example, an active time delay can be ended by pressing
a button on the Decision-Maker
r
MPAC 1500 controller.
Separate time delay bypass switches are not required.
See Figure 3 for accessory information.
M340+
Decision-Maker
r
MPAC
1500
Bypass (end) Time Delay
Switches
Integrated
Source Monitor
Integrated
Test Switch
Integrated
Override Switches
Integrated
Preferred Source Switch
Alarm Module required
(see Figure 4)
Current Meter (amps)
Current Sensing Kit required
(see Figure 6)
Plant Exerciser
Integrated
Manual Switch Operation
Supervised Transfer Control
Switch (see Figure 5)
Voltage/Frequency Meters Integrated
Load Shed Contact
Integrated Load Control
Function (one output
connection required)
Figure 3
Accessories
Accessory Modules
Optional accessory modules are listed in Figure 4. One
module mounting kit holds up to five accessory
modules.
Accessory Modules
Part Number
Module Mounting Assembly *
GM46258-S
Standard I/O Module
GM46888-S
High Voltage/Current I/O Module
GM46890-S
Alarm Module
GM40808-S
External Battery Supply Module
GM46889-S
* One mounting assembly holds up to 5 modules.
Figure 4
Accessory Modules for Decision-Maker
r
MPAC 1500
Other Accessories
Other Decision-Maker
r
MPAC 1500 accessories are
available.
See Figure 5.
Contact your local
distributor/dealer for more information.
Other MPAC 1500 Accessories
Part Number
Controller Disconnect Switch
GM46770-S3
Supervised Transfer Control
Switch
[
GM40807-S1
[
Includes alarm module GM40808-S.
Figure 5
Other Accessories
Current Sensing
If current sensing is required (i.e. for current [amps]
monitoring and display), obtain the appropriately rated
current sensing kit (with 3 m [10 ft.] harness) before
starting the conversion procedure. If the transfer switch
is equipped with current transformers (CTs), they will
need to be replaced with the new current transformers
during the controller conversion procedure.
See
Figure 6 for current sensing kit numbers. Check the
amp rating and number of phases of the transfer switch
and select the closest current sensing kit with an equal
or higher amp rating.
Kit Description
Current Sensing
Kit Number
Amps
Phases
200
3
GM89028-S3
200
1
GM89028-S21
400
3
GM89028-S6
400
1
GM89028-S24
1000
3
GM89028-S8
1000
1
GM89028-S26
1200
3
GM89028-S11
1200
1
GM89028-S28
2000
3
GM89028-S15
3000
3
GM89028-S17
Figure 6
Current Sensing Kits
Availability is subject to change without notice. Kohler Co. reserves
the right to change the design or specifications without notice and
without any obligation or liability whatsoever. Contact your local
Kohler
r
generator set distributor for availability.
2016 by Kohler Co. All rights reserved.
Summary of Contents for ZCB-6
Page 9: ...TT 1684 3 16 9 Figure 22 Conversion Kit Assembly...
Page 14: ...14 TT 1684 3 16 GM77826 Figure 37 Conversion Kit Harness GM77826 for Model ZCB 6...
Page 21: ...TT 1684 3 16 21 Figure 55 Current Sensing Kit Wiring Diagram GM47803...
Page 34: ...TT 1684 3 16 34 This page intentionally left blank...