- 10 -
■
Threshold value settings
During hysteresis mode
During window comparator mode
High mode/Low mode
L1:
OFF point/ON point
Threshold value upper limit
ON point
L2:
ON point/OFF point
Threshold value lower limit
Unused
■
Import reference mode settings
0: import reference mode OFF
1: import reference mode ON
Hysteresis mode selected
Window comparator mode 1 selected
L2
L1
Δ
L
Reference flow rate capture
ON
t
Switch
output
Hysteresis
Lr (ON point)
Reference pressure
L2 (OFF point)
Δ
L
Switch output
■
Reference Import Mode (in Hysteresis Mode)
0
Negative
pressure
Positive
pressure
0
*Operate the threshold value L1 as Lr, the same as when used in window comparator mode, High mode, and Low mode.
■
ΔL settings
ΔL settings in import reference mode
Threshold value Lr is set by importing a reference.
Threshold value Lr = reference value - ΔL
■
Response differential settings
Response differential settings for window comparator mode, as well as High and Low mode
H1: response differential for threshold value L1
ON point L1, OFF point = L1 + H1
H2: response differential for threshold value L2 (not used in High mode or Low mode)
ON point L2, OFF point = L2 - H2
■
ON delay settings
ON delay for preventing chattering of switch output
Not being turned ON prevents chattering, etc. when the time ON is shorter than the time for ON delay (Td).
Time settings for ON delay:
0: none
1: 5 ms
2: 10 ms
3: 50 ms
4: 100 ms
5: 500 ms
6: 1000 ms
t
0
L2 (OFF point)
L1 (ON lit)
Td