Output mode settings
Set the output mode for each channel.
0: Output OFF mode
Always output OFF
1: Hysteresis mode
Mode for setting the ON point and OFF point
2: Window comparator mode 1 (output cut when rising)
Mode for turning output ON within the set value range for L1 and L2 (OFF point depends on response differential setting)
Does not turn on when entering range while rising
3: Window comparator mode
Mode for turning output ON within the set value range for L1 and L2 (OFF point depends on response differential setting)
4: High mode
Mode for turning output ON when above the ON point (OFF point depends on response differential setting)
5: Low mode
Mode for turning output ON when below the ON point (OFF point depends on response differential setting)
■
Hysteresis Mode
L2 (OFF lit)
L1 (ON lit)
Switch output
0
Negative pressure
Positive pressure
0
L2(OFF
lit)
L1(ON lit)
When L1 < L2
When L1 > L2
No outputwhenL1= L2.
L1(ON
lit)
L2(OFF lit)