MIM-
MIM 01/0419
page
21
10.4.3 Temperature
10.4.3.1 Temperature
Unit
The displayed unit for the temperature measurement can be selected from various
default units. It is also possible to define a user-defined unit ("user"), in which case
the "user unit" must be programmed in °C.
e.g. Unit “user” = 50 °C, if T = 50 °C then the display shows 1 user.
10.4.3.2 Simulation
function
See section 10.4.5
10.4.4 Part
Volume
10.4.4.1 Counter
type
Absolute:
Regardless of the flow direction, the calculated partial volume is added to the
counters.
Bidirectional:
Depending on the flow direction, the calculated partial volume is added or
subtracted to the counters. If the measured flow value is negative, the volume
value goes down from measurement to measurement (possibly into the
negative range).
10.4.4.2
Unit of the part volume counter
The parameter "unit" defines the volume unit of all volume meters. The listed
volume units are available. When changing the volume unit, the current counter
readings are converted to the new volume unit.
10.4.4.3 Memory
reset
In this menu, the part quantity counter can be reset.
10.4.4.4 Simulation
function
See section 10.4.5
10.4.5 Simulation
function
With the simulation function, all available measured values can be simulated
independently of each other for a limited time. The simulated measured values
have full effect on the displays and outputs.
Each simulation started is automatically stopped after the time set in the "Sim Auto
Stop Time" (user service) parameter (1 to 30 min) or after the programmed intervals
have expired.
The following measured values can be simulated:
Volume flow, temperature and part quantity counter
The simulation starts as soon as the simulation is activated and the setting menu
is exited. The simulation is interrupted or stopped, if the setting menu is called up.
There are 3 different simulation types available for each purpose: