Operation
KEC-1
K01/1216
Page
34
of
43
8.3.2.1
Modbus Settings (2001…2005)
Modbus
Register
Register
Address
No.of
Byte
Data Type
Description
Default
Setting
Read
Write
Unit /Comment
2001
2000
2
UInt16
Modbus ID
1
R/W
Modbus ID 1…247
2002 2001 2 UInt16
Baudrate
4
R/W
0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 38400
2003 2002 2 UInt16
Parity
1
R/W
0 = none
1 = even
2 = odd
2004
2003
2
UInt16
Number of Stopbits
R/W
0 = 1 Stop Bit
1 = 2 Stop Bit
2005 2004 2 UInt16
Word
Order 0xABCD R/W
0xABCD = Big Endian
0xCDAB = Middle Endian
8.3.2.2
Values Register (1001 …1500)
Modbus
Register
Register
Address
No.of
Byte
Data Type
Description
Default
Read
Write
Unit /Comment
1101 1100 4
Float
Flow in m³/h
R
1109 1108 4
Float
Flow in Nm³/h
R
1117 1116 4
Float
Flow in m³/min
R
1125 1124 4
Float
Flow in Nm³/min
R
1133 1132 4
Float
Flow in ltr/h
R
1141 1140 4
Float
Flow in Nltr/h
R
1149 1148 4
Float
Flow in ltr/min
R
1157 1156 4
Float
Flow in Nltr/min
R
1165 1164 4
Float
Flow in ltr/s
R
1173 1172 4
Float
Flow in Nltr/s
R
1181 1180 4
Float
Flow in cfm
R
1189 1188 4
Float
Flow in Ncfm
R
1197 1196 4
Float
Flow in kg/h
R
1205 1204 4
Float
Flow in kg/min
R
1213 1212 4
Float
Flow in kg/s
R
1221 1220 4
Float
Flow in kW
R