Measuring range
KEC-1
K01/1216
Page
10
of
43
4.2
Measuring range flow KEC-1
The flow-/consumption sensor KEC-1 is available in 3 different versions:
Standard
max. measuring range of 92.7 m/s
Max–Version
max. measuring range of 185.0 m/s
High speed–Version
max. measuring range of 224 m/s
The sensors are programmed to pipe inner diameter of 53,1 mm this corresponds to analogue output
4- 20 mA of:
Standard
0 … 600 m³/h
Max–Version
0 ... 1197.59 m³/h
Highspeed–Version
0 … 1450.06 m³/h
In case of use in other inner pipe diameter the diameter, using the display version, the diameter has to
be set first.
For changing the inner pipe diameter and adjusting the 4…20 mA scaling, please refer to chapter
“Operation”.
The corresponding scale values for the respective version could be found in sections 4.2.1 to 4.2.3.
Example:
Pipe 1“, Inner diameter 25mm
Standard Version
0 … 122.2 m³/h
Max–Version Version
0 ... 1197.59 m³/h
Highspeed–Version
0 … 1450.06 m³/h