3.6.4
Temperature probe
Parameter name
Values
Calibration offset
-50 ...
0
... 50 (x 0.1ºC)
Sending period
0
... 255 (x 10 s, 0 = Disabled)
Send when change is greater than
0
... 255 (x 0.1ºC, 0 = Disabled)
Alarm function
Disabled
High temperature alarm
Low temperature alarm
High/low temperature alarms
High temperature alarm threshold
(If high temperature alarm is enabled)
-30 ...
30
... 125 (ºC)
Low temperature alarm threshold
(If low temperature alarm is enabled)
-30 ...
10
... 125 (ºC)
The
Calibration offset
,
Sending period
, and
Send when change is greater than
parameters are
equivalent to the corresponding parameters for the internal temperature probe (see
on page 45).
If the temperature cannot be read (for example because the temperature probe is broken,
or disconnected from the input) an error is signalled through a separate
[INx] Probe error
communication object.
An alarm function can be enable to detect high and/or low temperatures. This is done through
the
Alarm function
parameter. Also the thresholds for high and low temperature alarms can be
defined. The alarm condition is signalled through the
[INx] Temperature alarm
communication
object.
3.7
Scenes
3.7.1
General
Parameter name
Values
Send read requests at startup
No /
Yes
Scene actuator 1
[Checkbox]
...
Scene actuator 8
[Checkbox]
3.7
Scenes