In both cases, the current thermostat function (heating or cooling) is available at any time
through the
Heating/Cooling mode (status)
communication object.
Also, the
Heating / Cooling mode after programming
parameter defines the initial mode (either
“Heating” or “Cooling”) after an ETS download.
Thermostat on/off control
Parameter name
Values
Thermostat always ON
No
/ Yes
State after bus recovery
(Only if thermostat is NOT always ON)
Last state
/ Off / On
Switch ON upon operating mode reception
(Only if thermostat is NOT always ON)
No
/ Yes
The
Thermostat always ON
parameter determines whether the thermostat should always be on,
or whether it should be possible to switch it on and off through an associated communication
object.
If the thermostat is NOT always ON:
• Two communication objects are enabled (
On/Off
and
On/Off (status)
) to control operation
of the thermostat.
• A parameter
State after bus recovery
is available to define the state of the thermostat after
at startup, or after a bus recovery event (On, Off, or the last known state)
• A parameter
Switch ON upon operating mode reception
determines if the thermostat
should automatically switch on when it receives a request to change the current operating
mode.
Sending of status values
Parameter name
Values
Status sending delay after bus recovery
0
... 255 (x 1s, 0 = Disabled)
Parameter
Status sending delay after bus recovery
controls whether the initial value of the
thermostat’s status objects is sent to the bus at startup or after a bus recovery event. Values can
be sent after a configurable delay (1-255 seconds) or this function can be disabled by setting the
parameter to 0.