3.3 Electrical Installation
WARNING!
Shock potential.
Install the product with the power off.
Wire preparation
Note:
Use only shielded wires suitable for the ambient conditions. Connected cables and wires must
be rated for the current limit of the protective device for the circuit at minimum.
Conductor cross-sections
0.2
…
1.5 mm
2
, AWG 24
…
16
Stranded with ferrule or solid
01.
Strip 10 mm of insulation from the wire ends. Fit fine-stranded wires with ferrule.
01.
Insert the wire into the two-tier terminal (push-in version) without using tools. If necessary, open
the two-tier terminal with a screwdriver to make it easier to insert the wire. To remove the wire
from the two-tier terminal, use the screwdriver as shown.
02.
Alternatively, use screw terminals.
WARNING!
Shock Potential.
Maintain the necessary distances to the two-tier terminals and DIP
switches to maintain galvanic isolation.
Wiring
Note:
The current output must always terminate with a load.
Note:
For 2-channel devices, input signals 1 and 2 must come from the same speed sensor. The output
signals must only go to one controller.
Note:
When using the current input, U
S
, U
in
, and GND must be connected to the insertable jumper.
If voltage inputs are used, the current input must not be used. P16480: the DOT signal is available at
output 3.3.
01.
Connect the P16800 in accordance with the selected circuit (signal type, shielding, equipotential
bonding).
02.
Check that the wire is securely attached.