KMC Controls
Revision E
About the LAN controller
Specifications
6
Specifications
Processor
Motorola 68360, 32–bit, 33 MHz
Memory
Flash
2 megabytes, nonvolatile, operating programs
and data storage
RAM
2 megabytes, 72–hour capacitor backup
Inputs and Outputs
The KMD-5210 controller includes eight
universal I/O ports for optional input and
output modules. Connect up to eight KMD-5220
input modules, eight KMD-5221 output
modules or a combination of input and output
modules in any combination.
I/O Ports
Eight, 16–pin connectors. Software selectable as
analog or digital standard or custom units of
measure.
Inputs
16–bit analog-to-digital (A/D)
Software selectable as analog or digital standard
or custom units of measure. Install up to 8, 16
input modules for up to 128 universal inputs.
Output
12–bit digital to analog (D/A)
Communications
Tier 1
EIA–485 protocol at rates up to 38 kilobaud.
Connector type is a three-screw terminal block,
12–22 AWG wire.
Note:
Use the Tier 1 connection only when
replacing KMD–5110 MultiNet controllers and
Ethernet is not available. Contact KMC Controls
techncial support for networking details.
Tier 2 A and B
EIA–485 protocol at rates up to 38 kilobaud.
Connectors are three-screw terminal blocks,
12–22 AWG wire. Two ports, each of which
support up to 124 KMC Tier 2 controllers.
EIA–485
EIA–485 protocol at rates up to 38 kilobaud.
Connector is a three-screw terminal block,
12–22 AWG wire. Supports BACnet MS/TP in
KMD-5210–002.
Modem
EIA–232 in parallel with Computer B. Dial-in
and dial-out for with alarm and paging
capability, 9–Pin (DB-9).
Computer A and B
Two EIA–232 ports, operate up to 38.4 kilobaud.
Connectors are three-screw terminal blocks,
12–22 AWG wire.
Ethernet
10baseT, RJ–45 supports up to 31 networked
Tier 1 controllers and BACnet 802.3 in KMD-
5210–001
Summary of Contents for KMD-5210
Page 4: ...KMC Controls Revision E 4 ...
Page 12: ...KMC Controls Revision E About the LAN controller Safety Considerations 12 ...
Page 26: ...KMC Controls Revision E Installation Connecting to a Computer 26 ...
Page 30: ...KMC Controls Revision E Operation Resetting the controller 30 ...
Page 38: ...KMC Controls Revision E Configuration and programming System time keeping 38 ...