KMC Controls
Revision E
Configuration and programming
Configuring a controller with HCM
34
Ethernet routing table
The Ethernet routing table is a list that associates the KMC network addresses
assigned to Tier 1 controllers with the IP addresses required by the LAN
protocol. If the controller is not configured correctly, it will not communicate
with other controllers and may cause problems with the rest of the network.
Before starting the HCM initializing process you will need information about
the controller and the LAN which is listed in Table 4-2.
Note
Ethernet settings do not take effect in a controller until the power is cycled.
Ethernet troubleshooting
If the controller does not appear Network Status in the WinControl program,
try the following.
1. Obtain a crossover cable (available in most stores that carry network
products).
2. Connect the crossover cable between the Ethernet connection on your
computer and the Ethernet connector on the LAN Controller.
3. Open an MS-DOS window on your computer and Ping the controller’s IP
address. If the controller is operating correctly, you should receive a
response to the ping command.
If you are unfamiliar with the above steps, contact KMC Controls for
assistance.
Table 4-2 Tier 1 (LAN) controller Ethernet settings
Setting
Description
IP address
Supplied by network administrator. Enter the address next to the
panel address of the LAN Controller.
MTU
1400 or as supplied by system administrator
Gateway
Use default (255.255.255.255) unless a router (gateway) is located
between two Tier 1 controllers. The router IP address is supplied by
the network system administrator.
MAC address The MAC address is located on the white label on front of controller.
MAC addresses for KMC Controls products begins with 00-D0-6F.
Broadcast
sever
For controllers 1 - 16, select the
Broadcast Server
check box only for
the controller to which HCM is connected.
Select the
Broadcast Server
check box for all other controllers.
Interval
Sets the interval for the broadcast message. The broadcast message is
for KMD controllers and not a LAN broadcast message. The default
setting is 20 seconds.
Subnet mask
Set the Subnet Mask address to 255.255.255.0. or as supplied by
network system administrator.
Summary of Contents for KMD-5210
Page 4: ...KMC Controls Revision E 4 ...
Page 12: ...KMC Controls Revision E About the LAN controller Safety Considerations 12 ...
Page 26: ...KMC Controls Revision E Installation Connecting to a Computer 26 ...
Page 30: ...KMC Controls Revision E Operation Resetting the controller 30 ...
Page 38: ...KMC Controls Revision E Configuration and programming System time keeping 38 ...