Configuring a controller with HCM
32
Configuring a
controller with
HCM
Before placing a controller into service, it must be initialized and addressed
with the KMC
Hardware Configuration Manager
(HCM) software. HCM is
distributed with application programs; complete instructions for HCM are
included in the
H
ardware Configuration Manager
manual and the context sensitive
help system built into HCM.
Caution
The Hardware Configuration Manager sets all controllers on the Tier 2
network to the same parameters. To prevent disruption to other controllers on
the network, disconnect the network cables or remove the isolation bulbs on
the controller prior to starting HCM.
1. Start HCM, connect the controller to the computer and establish
communications with the controller.
2. Make the entries as described in the section
3. Setup the Ethernet routing table. See
4. If applicable, enter BACnet parameters. See
5. Cycle the power to the controller. The controller can now be connected to
a network and additional programming can be performed with
WinControl XL or the Acuity Configuration tool.
Note
Ethernet settings do not take effect in a controller until the power is cycled.
Summary of Contents for KMD-5210
Page 4: ...KMC Controls Revision E 4 ...
Page 12: ...KMC Controls Revision E About the LAN controller Safety Considerations 12 ...
Page 26: ...KMC Controls Revision E Installation Connecting to a Computer 26 ...
Page 30: ...KMC Controls Revision E Operation Resetting the controller 30 ...
Page 38: ...KMC Controls Revision E Configuration and programming System time keeping 38 ...