Short-circuit protected
Loads up to 10 mA at 0–12 volts DC
8-bit PWM digital-to-analog conversion
Relay outputs
Relay outputs are configured to represent BACnet binary objects. The
outputs control on/off valves, speeds for three-speed fans, fan start circuits,
or other equipment that requires an on or off input signal.
All relay outputs are normally open, SPST, Form “A” relays
1 Ampere maximum per relay at 24 volts AC or DC for each output.
Maximum for all relay outputs is 3 amperes (72VA).
Connectors
Screw terminal block mounted to backplate
Wire size 14-22 AWG
Communications—BACnet MS/TP
Integral peer-to-peer BACnet MS/TP network communications.
Network speeds from 9600 to 76,800 baud.
Front panel configurable device instance, MAC address, and baud.
Automatic baud detection.
Screw terminal block mounted to backplate. Wire size 14–22 AWG
Meets or exceeds ANSI/ASHRAE BACnet Standard 135-2008 for
Application Specific Controllers
Accuracy–temperature only models
Type
Thermistor
Accuracy
±0.36° F (±0.2° C)
Resistance
10,000 Ω at 77° F (25° C)
Operating range
48 to 96° F (8.8 to 35.5° C)
Accuracy–temperature and humidity models
Temperature Sensor
Type
CMOS
Accuracy
±0.9° F offset (±0.5° C) from 40° to 104° F
(4.4 to 40° C)
Resolution
±0.1°F (±0.1° C)
Operating range
36 to 120° F (2.2 to 48.8° C)
Response time
5 to 30 seconds
Installation, Operation, and Application Guide for AppStat
Section 1: Introduction to the AppStat
Revision G
9
Summary of Contents for BAC-4000 series
Page 6: ...Contents KMC Controls Inc 6 Revision G ...
Page 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Page 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Page 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Page 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Page 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...