Procedure
Steps
Display
4
Set the fan delay.
From the SYSTEM menu choose FAN OFF
DELAY to set the time the system fan will
continue to run after the last heating or cooling
stage is turned off.
Back
Enter
Cncl
FAN OFF DELAY
2 2 mins
5
Set the occupied fan
control.
From the SYSTEM menu choose OCCUPIED
FAN to choose the following:
When ON, the fan will run continuously
when the AppStat schedule is ON (occupied).
When the AppStat schedule is OFF
(Unoccupied) the fan will run only when
there is a call for heating or cooling.
Back
Enter
Cncl
OCCUPIED FAN:
ON
OFF
6
Set up staged cooling
and heating.
To set up staged cooling and heating do the
following:
1.
From the SYSTEM menu choose MIN OFF
TIME to enter the time a stage must remain
turned off before it can be turned on again.
2.
From the SYSTEM menu choose STAGE
DELAY to enter the time the first stage must
remain turned on before the second stage
can be turned on.
Back
Enter
Cncl
MINOFF TIME:
5 mins
Back
Enter
Cncl
STAGE DELAY:
10 mins
Set up roof top unit system options (continued)
Section 4: Commissioning functions
KMC Controls, Inc.
54
Revision G
Summary of Contents for BAC-4000 series
Page 6: ...Contents KMC Controls Inc 6 Revision G ...
Page 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Page 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Page 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Page 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Page 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...