Procedure
Steps
Display
4
Set the fan delay.
From the SYSTEM menu choose FAN DELAY
OFF to set the time the system fan will continue
to run after the last heating or cooling stage is
turned off.
Back
Enter
Cncl
FAN OFF DELAY
2 2 mins
5
Set the occupied fan
control.
From the SYSTEM menu choose OCCUPIED
FAN to choose the following:
When ON, the fan will run continuously
when the schedule is occupied (On).
When the schedule is unoccupied (Off) the
fan will run only when there is a call for
heating or cooling.
Back
Enter
Cncl
OCCUPIED FAN:
ON
OFF
6
Set the valve action.
Select one of the valve actions from the
SYSTEM menu. Not all choices apply to every
application.
CL VALVE ACTION—(Four-pipe only)
HT VLV ACTION—(Four-pipe only)
VLV ACTION—(Two-pipe only)
Valve action selections are the same for all three
types of valves.
NORMAL OPEN—The valve changes from
fully open to fully closed as the AppStat
varies the valve output from 0 to 10 volts.
NORMAL CLOSED—The valve changes
from fully closed to fully open as the
AppStat varies the valve output from 0 to 10
volts.
CL VLV ACTION:
NORMAL OPEN
NORMAL CLOSED
Del
Enter
Cncl
HT VLV ACTION:
NORMAL OPEN
NORMAL CLOSED
Del
Enter
Cncl
VLV ACTION:
NORMAL OPEN
NORMAL CLOSED
Del
Enter
Cncl
Set up fan coil unit system options (continued)
Installation, Operation, and Application Guide for AppStat
Section 4: Commissioning functions
Revision G
51
Summary of Contents for BAC-4000 series
Page 6: ...Contents KMC Controls Inc 6 Revision G ...
Page 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Page 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Page 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Page 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Page 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...