SMY133-SMY134-SMP133 Operating Manual
Instrument Auxiliary Power Supply Voltage
model
„U“
„L“
„S“
rated (nominal) auxiliary voltage range
110 ÷ 250 V
AC
23 ÷ 68 V
DC
12 ÷ 32 V
DC
aux. voltage range AC: f=40÷100 Hz;
DC:
100 ÷ 275 V
AC
90 ÷ 350 V
DC
20 ÷ 50 V
AC
20 ÷ 75 V
DC
10 ÷ 26 V
AC
10 ÷ 36 V
DC
power
8 VA / 4 W
overvoltage cat.
III
pollution degree
2
connection
isolated, polarity free
power outage backup (SMP 133 only)
technology
backup time
supercapacitors; instrument measuring core backup only
> 3 sec after being powered from external power
supply for > 5 min
> 1 sec after being powered from external power
supply for > 1.5 min
\
„X/333mV“ Instrument Model Auxiliary Voltage for Current Sensors
connection
non-isolated (connected with the instrument internal circuitry)
output voltage
+5 V
DC
± 5 %
maximum permanent load
60 mA
DC
short-circuit current, max. duration
approx. 100 mA
DC,
5
seconds
Measured Quantities - Temperature
T
I
- (internal sensor, measured value affected by the instrument power dissipation)
measuring range
- 40 ÷ 80°C
measurement uncertainty
± 2 ºC
T
E
– External Pt100 Temperature Sensor Input
(„AT“ models only)
measuring range
- 50 ÷ 150 º
measurement uncertainty
± 2 ºC
notes
- External temperature input is insulated neither from instrument
internal circuitry nor from residual current input
- The terminals T- and IΔ12 are connected internally, do not connect
signals of different potential !
- Maximum length of connection cable is 3 meters ! Otherwise, EMC-
immunity of the instrument can be degraded.
80